セキュリティセンサー ADEMCO 5809のPDF インストレーション・インストラクションをオンラインで閲覧またはダウンロードできます。ADEMCO 5809 2 ページ。 Rate-of-rise heat detector/transmitter

ADEMCO 5809 インストレーション・インストラクション
®
GENERAL INFORMATION
The Ademco 5809 Rate-of-Rise Heat Detector/Transmitter is
intended for use with wireless alarm systems that support QED
5800 series devices, and contains a built-in transmitter which
can send alarm, supervisory and battery condition messages to
the system's receiver/control unit. Refer to the QED wireless
system's instructions for the maximum number of transmitters
that can be supported.
The 5809 combines both rate-of-rise and fixed temperature
sensors. Fires typically cause a rapid rise in temperature in the
surrounding area. The 5809's rate-of-rise thermostat senses the
rise in temperature and signals an alarm if the rise is 15°F (8°C)
or more per minute. A built-in fixed temperature sensor will
also signal an alarm if the ambient temperature rises above
135°F (57°C).
NOTE: If the fixed temperature sensor activates, the
5809 must be replaced.
The 5809 is powered by a 3-volt lithium battery. If the battery
voltage gets too low, the 5809 sends a low battery signal to the
control panel.
The 5809 also features a tamper switch, which causes a trouble
signal to be sent to the control if the unit is removed from the
mounting base.
A built-in activation button, located on the PC board assembly,
is used when programming the unit's serial number at the
control and when testing the unit.
INSTALLING THE BATTERY
Important Notes:
• Use 3-volt lithium battery:
Duracell DL123A or
Panasonic/Sanyo/Varta CR123A.
• Observe polarity.
• When replacing the battery, wait at least 30 seconds after
removing the old battery, before installing the new one.
Remove the detector from its base and install a 3-volt lithium
battery as shown below.
+
BATTERY
INSTALLATION INSTRUCTIONS
RATE-OF-RISE HEAT DETECTOR/TRANSMITTER
For use with QED control panels ONLY!
PROGRAMMING THE UNIT
The transmitter's serial number must be enrolled in the QED
control panel before usage in the system. The QED control unit's
installation
instructions
provide
procedures for enrolling transmitter serial numbers. Before
programming, do the following:
1. Remove the unit assembly from its mounting base by
twisting counter-clockwise and lifting.
2. Install the battery (if not already installed). Observe polarity!
3. Enter the control's programming mode and follow the
control's programming instructions.
this transmitter at the control, note the following:
Input Type = 3 (Supervised RF)
Loop Number = 1
Transmit from the detector when prompted (momentarily
press the activation button located on the exposed
transmitter PC board, install battery, etc.). You can also
manually enter the detector's serial number.
4. Test the detector after enrolling into the system. Refer to the
Testing section.
ACTIVATION
BUTTON
MOUNTING THE DETECTOR
You can mount the 5809 on a wall or ceiling within the
protection area:
• Wall Mounting: Mount the detector 4"-6" from the ceiling.
• Ceiling Mounting: Mount the detector at least 4" from any
wall. Make sure the normal ceiling temperature will not
exceed 100°F.
• Refer to NFPA Standard 72 for detector spacing and other
requirements.
Maximum spacing for UL installations is
50'x50'.
• Avoid mounting the detector near heat generating devices
(e.g. ovens, heat vents, furnaces, boilers).
IMPORTANT:
Heat detectors should be used for
property protection.
not be placed solely on heat detectors
for life safety.
involved, smoke detectors MUST
also be used. Detectors must not be
painted.
Previous Menu
N8583V1 5/98
5809
detailed
programming
When programming
BATTERY
Reliance should
When life safety is