9 Parameter setting
Parameters can be set before installation and set-up of the unit or during opera-
tion.
If you change parameters during operation, this will influence the function
of the plant.
► Ensure that there will be no malfunctions in your plant.
During parameter setting the unit remains in the operating mode. It continues
to monitor with the existing parameter until the parameter setting has been
completed.
9.1 Parameter setting in general
1. Change from RUN mode to the main menu
2. Selection of the requested parameter
3. Change to setting mode
4. Modification of the parameter value
5. Acknowledgement of the set parameter value
6. Return to the RUN mode
10 Troubleshooting
Display
[Err]
Off
[PArA]
[cr.UL]
[cr.OL]
[ Locked via key] Warning Setting pushbuttons on the unit locked, parameter change
16
Type
Description
Error
Unit faulty / malfunction
Error
Supply voltage too low
or setting diS.B = OFF
Error
Parameter setting outside the valid range
Error
Measured value smaller than -30 %, critically low
temperature
Error
Measured value greater than 130 %, critical excess flow /
temperature
rejected.
[●]
[▲] or [▼]
[●]
[▲] or [▼] > 1 s
[●]
> 30 seconds (timeout) or
press [▲] + [▼] simultaneously
until the RUN mode is reached.