Technical Data For PSS0524-100
Input (AC)
Nominal input voltage
Voltage range
Frequency
Nominal current
Inrush current limitation. I2t (+25 °C) typ.
Leakage current
Output (DC)
Nominal output voltage / adjustment range
Output Voltage Tolerance
Output power*
Output current
PARD (ripple and noise) (20MHz)
Start-up time
Hold-up time
Rise time
Dynamic response (overshoot and undershoot O/P voltage)
Start-up with capacitive loads
Efficiency
Line regulation
Load regulation
General Data
Type of housing
Dimensions (L x W x H)
Weight
MTBF
Connection method
Noise
Cooling
Terminal input/output
Wire size / torque
Shock test (non-operating)
Vibration (non-operating)
Safety / Environmental
EMC / Emissions
Immunity
Voltage dips
Galvanic isolation
Approvals
RoHS Compliant
Operating temperature
Storage temperature
Humidity
All parameters are specified at 25°C (77°F)
* Operating to 70 °C (158°F) possible with a linear derating to half power from 50°C to 70°C (122°F to 158°F)
V1: +/- 2% (initial setpoint tolerance from factory); V2: fixed
V1: 0.3-4.0 Amp; V2: 0.8-7.0 Amp (each output can work within the current range, but ensure that the total output power does not exceed 100W)
V1: <200mVpp; V2: <80mVpp (each measured with AC coupling mode, and in parallel with 0.1uF ceramic capacitor and 47uF electrolytic capacitor.)
> 15ms @ 115VAC, >80ms @ 230VAC with 100% load
+/-5%@V1: 0-100% rated load and V2: 60%rated load and vice versa (Slew rate: 0.1A/uS)
<1% typical (@85 to 264 VAC input, V1: 20-100% rated load and V2: 60% rated load and vice versa)
178 mm x 97 mm x 38 mm (7.0 in x 3.82 in x 1.50 in)
IEC60068-2-27, 30G (300m/S²) for a duration of 18ms 3 times per direction, 18 times in total
IEC60068-2-6, 10Hz to 150Hz @ 50m/S² (5G peak); 20 min per axis for all X, Y, Z direction
IEC61000-4-2; IEC61000-4-3; IEC61000-4-4; IEC61000-4-5; IEC61006-4-6; IEC61006-4-8; IEC61006-4-11; IEC61006-4-12
IEC61000-4-11 100% dip; 1 cycle (20ms); self recoverable
Input to Output : 3KVAC, Input to Ground : 1.5KVAC, Output to Ground : 0.5KVAC
UR/cUR recognized to UL60950-1 and CSA C22.2 No. 60950-1 (file no. E198298); CB test certificate and report to IEC60950-1, CE (EMC and Low Voltage directive)
100-240 VAC / 125-250 VDC
85-264 VAC (DC input range 125-375 VDC)
47-63 Hz (0 Hz @ DC input)
2.0A max. @ 115 VAC, 1.1A max. @ 230 VAC
< 50A @ 115 VAC, < 100A @ 230 VAC
< 1 mA @ 240 VAC
V1: 24 VDC / 22.8-26.4 VDC; V2: 5 VDC / fixed
100W
<1000ms@100% load and typical line input
V1: <30ms; V2: <20ms @100% load
V1: 4000uF max
> 84% @ 115 VAC & > 86% @ 230 VAC
< 0.5% typical (@ 85-264VAC input)
Aluminum
0.52 kg (1.15 lb)
> 700,000 hrs.
Screw connection
Sound pressure level (SPL) < 40 dBA
Convection
M3.5 x 7 Pins (Rated 300V/15A)
0.82-2.08 mm² (AWG 18-14) / 1.3 Nm (11.3 in-lb)
FCC Title 47, Class B/EN55032;CISPR32, Class B
E198298
Yes
-10 °C to +70 °C* (14°F to 158°F)
-25 °C to +85 °C (-13°F to 185°F)
< 95 % RH non-condensing