- ページ 4
I/Oシステム Automationdirect.com Productivity 2000 P2-08NASのPDF マニュアルをオンラインで閲覧またはダウンロードできます。Automationdirect.com Productivity 2000 P2-08NAS 4 ページ。 Ac isolated input
WARNING:
To minimize the risk of potential safety problems, you
should follow all applicable local and national codes that regulate
the installation and operation of your equipment. These codes
vary from area to area and it is your responsibility to determine
which codes should be followed, and to verify that the equipment,
installation, and operation are in compliance with the latest revision
of these codes.
Equipment damage or serious injury to personnel can result
from the failure to follow all applicable codes and standards. We
do not guarantee the products described in this publication are
suitable for your particular application, nor do we assume any
responsibility for your product design, installation, or operation.
If you have any questions concerning the installation or
operation of this equipment, or if you need additional information,
please call Technical Support at 770-844-4200.
This publication is based on information that was available at
the time it was printed. At AutomationDirect.com® we constantly
strive to improve our products and services, so we reserve the right
to make changes to the products and/or publications at any time
without notice and without any obligation. This publication may also
discuss features that may not be available in certain revisions of
the product.
Removable Terminal Block Specifications
Part Number
P2-RTB
Number of
18 Screw Terminals
Positions
Wire Range
30–16 AWG (0.051 – 1.31 sq. mm)
Solid / Stranded Conductor
3/64 in (1.2 mm) Insulation Max.
1/4 in (6–7 mm) Strip Length
Conductors
"USE COPPER CONDUCTORS, 75°C" or Equivalent
Screw Driver Width
Screw Size
Screw Torque
2.5 lb∙in (0.28 N∙m)
4
www.productivity2000.com
P2-RTB-1
18 Spring Clamp Terminals
28–16 AWG (0.081 – 1.31 mm²)
Solid / Stranded Conductor
3/64 in (1.2 mm) Insulation Max.
19/64 in (7–8) mm Strip Length
1/8 inch (3.8 mm) Maximum
M2
N/A
N/A
General Specifications
Operating Temperature
0° to 60°C (32° to 140°F),
Storage Temperature
-20° to 70°C (-4° to 158°F)
Humidity
5 to 95% (non-condensing)
Environmental Air
No corrosive gases permitted
Vibration
IEC60068-2-6 (Test Fc)
Shock
IEC60068-2-27 (Test Ea)
Field to Logic Side Isolation
1800VAC applied for 1 second
Insulation Resistance
>10MΩ @ 500VDC
Heat Dissipation
600mW
Enclosure Type
Open Equipment
Module Keying to Backplane Electronic
Module Location
Any I/O slot in Productivity2000 System.
Field Wiring
Use ZIPLink Wiring System or removable terminal
block (not included). See "Wiring Options" on
page 3.
EU Directive
See the "EU Directive" topic in the Productivity
Suite Help File. Information can also be obtained
at: www.productivity2000.com
Connector Type
18 position terminal block
(sold separately)
Weight
85g (2.9 oz)
Agency Approvals
UL61010-2-201 file E139594, Canada & USA
CE (EMC: EN61131-2*, SAFETY: EN61010-2-201)
*Meets EMC and Safety requirements. See the D.O.C. for details.
Document Name
P2-08NAS-DS
Copyright 2016, AutomationDirect.com Incorporated/All Rights Reserved Worldwide
Tech Support 770-844-4200
Edition/Revision
Date
2nd Ed.
9/26/2016