- ページ 2
コントロールユニット Automationdirect.com Productivity 2000 P2-04DAのPDF マニュアルをオンラインで閲覧またはダウンロードできます。Automationdirect.com Productivity 2000 P2-04DA 8 ページ。 Analog output
General Specifications
Operating Temperature
0º to 60ºC (32º to 140ºF)
Storage Temperature
-20º to 70ºC (-4º to 158ºF)
Humidity
5 to 95% (non-condensing)
Environmental Air
No corrosive gases permitted
Vibration
IEC60068-2-6 (Test Fc)
Shock
IEC60068-2-27 (Test Ea)
Field to Logic Side Isolation
1800VAC applied for 1 second
Insulation Resistance
> 10MΩ @ 500VDC
Heat Dissipation
3.6W
Enclosure Type
Open Equipment
UL508 File E139594, Canada & USA
Agency Approvals
CE (EN61131-2*)
Module Keying to Backplane
Electronic
Module Location
Any I/O slot in a Productivity2000 System
Use ZIPLink Wiring System or removable terminal block
Field Wiring
(not included). See "Wiring Options" on page 5.
See the "EU Directive" topic in the Productivity2000
EU Directive
Help File. Information can also be obtained at:
www.productivity2000.com
Connector Type (not included) 18-position removable terminal block
Weight
90g (3.2 oz)
*Meets EMC and Safety requirements. See the D.O.C. for details.
2
www.productivity2000.com
Output Specifications
Output Channels
4
1) ±10VDC
Module Signal Output Ranges
2) 4-20 mA (sink or source per channel)
Signal Resolution
16-bit
±10V = 305μV/count
Resolution Value of LSB
4-20 mA = 0.244 μA/count
(least significant bit)
1 LSB = 1 count
0 to 65535 counts uni-polar and
Data Range
-32768 to +32767 counts bi-polar
Voltage outputs sources/sinking at 10mA max, or
Output Type
Current outputs sink or source at 20mA max.
Output Value in Fault Mode
Voltage outputs 0V or 0mA current outputs
>1000Ω voltage outputs (19.2 - 30 VDC)
0 - 755Ω Sinking, 0 - 600Ω Sourcing (19.2 VDC)
Load Impedance
0 - 875Ω Sinking, 0 - 700Ω Sourcing (21.6 VDC)
(Minimum External Power Supply)
0 - 1000Ω Sinking, 0 - 855Ω Sourcing (24VDC)
0 - 1110Ω Sinking, 0 - 970Ω Sourcing (26.4 VDC)
0 - 1350Ω Sinking, 0 - 1150Ω Sourcing (30VDC)
Maximum Capacitive Load
0.01μF maximum voltage outputs
Maximum Inductive Load
1mH maximum current outputs
Allowed Load Type
Grounded
Maximum Inaccuracy (% of range)
0.1% voltage, 0.1% current (including temperature drift)
Maximum Full Scale Calibration
±0.025% of range maximum voltage outputs
Error (not including offset error)
±0.025% of range maximum current outputs
Maximum Offset Calibration Error
±0.025% of range maximum
±25ppm/°C max f.s. calibration change
Accuracy vs. Temperature
(±0.0025% of range/°C)
Max Crosstalk
-80dB, 6 LSB
±16 LSB maximum (±0.025% of full scale)
Linearity Error (End to End)
Monotonic with no missing codes
Output Stability and Repeatability
±10 LSB after 10 minute warm-up (typical)
Output Ripple
0.05% of Full Scale
Output Setting Time
0.3 ms max, 5μs min (full scale change)
All Channel Update Rate
0.6 ms
Voltage Outputs current limited to 35mA typical
Maximum Continuous Overload
Current Outputs open circuit protected
15VDC Peak Output Voltage
Type of Output Protection
Current outputs current limited to <=20mA
Output Signal (power-up,-down)
0V voltage outputs, 0mA current outputs
94mA voltage operation 4 channels
External DC Power Required
130mA current operation 4 channels
24VDC -20% / +25%
Tech Support 770-844-4200