- ページ 12

エアコン Aire-Flo 36のPDF 取付説明書をオンラインで閲覧またはダウンロードできます。Aire-Flo 36 18 ページ。 14 seer

Aire-Flo 36 取付説明書
STEP 4 -- ELECTRICAL (CONTINUED) -- High Voltage and Field Control Wiring
The following illustration provide an example of control wiring connections when using standard thermostat.
ROUTING HIGH VOLTAGE, GROUND AND CONTROL WIRING
HIGH VOLTAGE / GROUND WIRES
Any excess high voltage field wiring should be
trimmed and secured away from any low voltage field
wiring. To facilitate a conduit, a cutout is located in the
bottom of the control panel. Connect conduit to the
control panel using a proper conduit fitting.
NOTE - Wire tie provides low voltage control wire strain
relief and maintains separation of field-installed low and
high voltage circuits.
NOTE - For proper voltages, select thermostat wire
(control wires) gauge per table above.
NOTE - Do not bundle any excess 24VAC control
wires inside control panel.
Install low voltage wiring from outdoor to indoor unit
and from thermostat to indoor unit as illustrated.
A - Run 24VAC control wires through hole with grommet
and secure with provided wire tie.
B - Make 24VAC thermostat wire connections. Locate
the two wires from the contactor and make
connection using field-provided wire nuts:
Yellow to Y1
Black to C (common)

FIELD CONTROL WIRING

THERMOSTAT
POWER
R
HEAT
W1
COOLING
Y
INDOOR BLOWER
G
COMMON
C
WIRE RUN LENGTH
LESS THAN 100' (30 METERS)
MORE THAN 100' (30 METERS) 16
FIGURE 12
Page 12
INDOOR UNIT
R
W
YELLOW
OUTDOOR UNIT
Y1
Y
G
BLACK
C
C
AWG# INSULATION TYPE
18
TEMPERATURE RATING
35ºC MINIMUM.