REMOTE DI ENABLE SETTINGS INSTRUCTION
CXE and CX(A)E remote enable function.
Fig 1.. ICPlus 915 controller wiring.
CXE and CX(A)E units with Eliwell ICPlus915 controller have Digital Input, which may be used to Enable controller or
put in Standby Mode remotely. Fig 1. shows how to use Volt-free Digital Input. After wiring input you should change
parameters H11 and H13, so controller know how it should operate in accordance with DI status. We recommend to
set H11 – 3 (Outputs stopped); H13 – noP(2) or ncP(3) dependant on operation logic you want.
Fig 2. ICPlus 915 controller parameters.
NOTE: Even if controller switch Outdoor unit OFF, Indoor fan will still run.
User's Password is not enabled by default – 0.
Default Installer's Password is – 15.