- ページ 4

温度コントローラー Autonics TCN4M SeriesのPDF 製品マニュアルをオンラインで閲覧またはダウンロードできます。Autonics TCN4M Series 6 ページ。 Dual display pid temperature controller
Autonics TCN4M Series にも: マニュアル (2 ページ), 取扱説明書 (2 ページ), マニュアル (13 ページ)

Autonics TCN4M Series 製品マニュアル
Connections
■ TCN4S
1
SSR OUT
12 VDCᜡ ±2V
20 mA Max.
2
3
4
5
-
SOURCE
100-240 VACᜠ
+
6
5 VA 50/60 Hz,
24 VACᜠ 5 VA 50/60 Hz,
24-48 VDCᜡ 3 W
■ TCN4S-□-P
SSR OUT
12 VDCᜡ ±2V
20 mA Max.
Relay OUT
250 VACᜠ 3A 1a
30 VDCᜡ 3A 1a
SOURCE
100-240 VACᜠ
5 VA 50/60 Hz,
24 VACᜠ 5 VA 50/60 Hz,
24-48 VDCᜡ 3 W
■ TCN4M
1
2
3
4
SSR OUT:
12 VDCᜡ ±2V
20 mA Max.
5
6
Relay OUT:
250 VACᜠ 3A 1a
30 VDCᜡ 3A 1a
7
8
-
SOURCE:
100-240 VACᜠ
+
9
5 VA 50/60 Hz,
24 VACᜠ 5 VA 50/60 Hz,
24-48 VDCᜡ 3 W
■ TCN4H/L
1
2
3
4
5
6
7
SSR OUT:
12 VDCᜡ ±2 V
20 mA Max.
8
9
10
11
SOURCE:
-
100-240 VACᜠ
+
12
5 VA 50/60 Hz,
24 VACᜠ 5 VA 50/60 Hz,
24-48 VDCᜡ 3 W
7
AL1 OUT
250 VACᜠ 1A 1a
8
AL2 OUT
250 VACᜠ 1A 1a
9
Relay OUT:
B' RTD
TC
250 VACᜠ 3A 1a
10
30 VDCᜡ 3A 1a
-
B
+
11
A
12
SENSOR
AL1 OUT
250 VACᜠ
1A 1a
AL2 OUT
250 VACᜠ
1A 1a
B'
B
TC
A
RTD
10
11
12
13
AL1 OUT:
250 VACᜠ
1A 1a
14
AL2 OUT:
15
250 VACᜠ
1A 1a
B' RTD TC
16
B
17
A
18
SENSOR
13
14
15
16
17
18
19
AL1 OUT:
250 VACᜠ
1A 1a
20
AL2 OUT:
250 VACᜠ
21
1A 1a
B' RTD TC
22
Relay OUT:
-
250 VACᜠ 3A 1a
B
+
30 VDCᜡ 3A 1a
23
A
24
SENSOR

Mode Setting

[MODE], [◀], [▲], [▼]
[MODE] 2 sec
RUN
[MODE] 4 sec
[◀] + [▲] + [▼] over 5
sec
[▲] + [▼] over 3 sec

Parameter Setting

• Some parameters are activated/deactivated depending on the model or setting of
other parameters. Refer to the description of each item.
• The setting range in parentheses is for using the decimal point display in the input
specification.
• If there is no key input for more than 30 seconds in each parameter, it returns to RUN
mode.
• When pressing the [MODE] key within 1 second after returning to the operation mode
from the parameter group, it will enter the parameter group before returning.
• [MODE] key: Saves the current parameter setting value and moves to the next
parameter.
[◀] key: Checks the fixed item / Moves the row when changing the set value
[▲], [▼] keys: Selects the parameter / Changes the set value
• Recommended parameter setting sequence: Parameter 2 group → Parameter 1 group
→ SV setting mode
■ Parameter 1 group
Parameter
Display Default Setting range
-
AL1 alarm
1-1
+
temperature
AL1
AL2 alarm
1-2
temperature
AL2
1-3
Auto tuning
Proportional
1-4
band
1-5
Integral time
Derivative
1-6
time
1-7
Manual reset
REST
1-8
Hysteresis
HYS
Move digits: [◀]
SV setting
Change value: [▲], [▼]
Save: [MODE]
→ Parameter 1 group
[MODE] over 3 sec
→ Parameter 2 group
[MODE] over 3 sec
Parameter reset
Auto
Digital input key
Auto
Deviation alarm: -F.S. to F.S. ℃/℉
1250
Absolute value alarm: Within input range
1250
OFF OFF: Stop, ON: Execution
AT
01)0 0.1 to 999.9 ℃/℉
P
0000 0 (OFF) to 9999 sec
I
0000 0 (OFF) to 9999 sec
D
05)0 0.0 to 100.0%
002 1 to 100 (0.1 to 50.0) ℃/℉
RUN
Condition
2-12/14
alarm
operation:
AM1 to AM6
2-8 Control
type: PID
2-8 Control
type: PID &
1-5 Integral
time: 0
2-8 Control
type: ONOF