Wiring and Configuration
Either 24VAC or 24VDC may be used to power the
MRLDS-250. Connect wiring to the appropriate terminal
locations. Use two wires, between 14 and 22 AWG.
Refer to Figure 3 for AC wiring (left) or DC wiring (right):
Figure 3 - Supply and Power Wiring Options
WARNING: The MRLDS-250 must be powered by:
• A suitable UL 60950/CSA certified power supply
that is isolated from line voltage by double
insulation.
• An appropriately rated UL listed/CA Class 2
Transformer; a 10VA Transformer is
recommended.
• For multiple devices cascaded, a 50VA Class 2
Transformer is recommended.
Figure 4 - Power Wiring of a Device Network
The MRLDS-250 provides an analog output signal that is
proportional to the level of gas detected. Connect two
18 to 20 AWG wires to terminal block positions 5 and 6
(see Figure 5A), noting ground and signal polarity.
Make relay connections (NO, NC, or both) using 18 to 20
AWG wires to terminal block positions 10, 11, and 12
(see Figure 5B), noting normally open, normally closed,
and common connectors.
Document Part # 026-4413 Rev 2
©2018 Emerson Climate Technologies Retail Solutions, Inc. This document may be photocopied for personal use.
Visit our website at http://www.emerson.com for the latest technical documentation and updates.
Figure 5A - Analog Output Wiring
Figure 5B - Sample Relay Output Wiring
NOTE: For MODBUS network communications wiring,
use only 18-24 AWG shielded twisted pair wire with 120
ohm characteristic impedance.
Figure 6 - MODBUS Network Communication Wiring