All loop statuses report on the isolator points, unlike the IDNet 2 Sprinkler Card where card status points are used to report the short and open
statuses of the loops.
Supported loop statuses:
You can make isolator devices public on the network, so that the loop status is available at external nodes, instead of reporting in the common trouble
point.
• If expansion loop cards are programmed but not connected, No Answer troubles indicate for those devices.
• If the loop card is present but not programmed, an Extra Device card status trouble indicates for the card, and the appropriate address is
logged in the trouble log: 253, 254, or both.

Card specifications

Operating conditions:
Operating temperature range
Operating humidity range
Electrical specifications:
Channel voltage to remote devices
Earth detection threshold
Card supply requirements
Comm wiring distance
Operating conditions:
Operating temperature range
Operating humidity range
Electrical specifications:
Channel voltage to remote devices
Earth detection threshold
Card supply requirements
Comm wiring distance
© 2021 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision and are subject to change without notice. Additional listings may be applicable, contact your local
AUTOPULSE® product supplier for the latest status. Listings and approvals and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. NFPA 72 and National Fire Alarm Code are
registered trademarks of the National Fire Protection Association (NFPA).
Table 4: Loop troubles
• Loop connected OFF
• Loop isolated ON
• Break in loop wiring OPEN CKT TROUBLE
• Short circuit SHORT CKT TROUBLE
Table 5: Sprinkler card specifications
32°F - 120°F (0°C - 49°C).
Up to 93% relative humidity at 90°F (32°C), non-condensing.
30 VDC (normal): 35 VDC maximum.
During an alarm or when activating large quantity of device outputs, the channel output voltage is
increased to 35 VDC. The data rate is 3333 bps.
Output circuits are supervised and power-limited.
10k ohms minimum from either positive or negative terminals.
19.5 V - 32 V / 350 mA maximum. 100 mA for the first device,
0.8 mA for each additional IDNet device.
See Table 2.
Table 6: IDNet loop card specifications
32°F - 120°F (0°C - 49°C).
Up to 93% relative humidity at 90°F (32°C), non-condensing.
30 VDC (normal): 35 VDC maximum.
During an alarm or when activating large quantity of device outputs, the channel output voltage is
increased to 35 VDC.
The data rate is 3333 bps.
Output circuits are supervised and power-limited.
10k ohms minimum from either positive or negative terminals.
19.5 V - 32 V.
See Table 2.