1.
If you are replacing an existing personality module that is already wired with an identical
personality module, and if there is no fault with the terminal block, leave wiring connected to
the terminal block, and disconnect the terminal block from the personality module by gently
rocking the terminal block from side to side until it pops out. Conversely, if there is a fault
with the terminal block, label wires coming in so you can transfer the wires to the correct
positions on the new terminal block. To wire an all-new module, see Wiring the Module.
Detaching the Terminal Block with Wires Still Attached
2.
Using a ¼" slotted blade screwdriver, loosen the captive fastening screw at the top of the
personality module and slide the module straight out of the slot.
Removing a Personality Module
FB3000 RTU HART
®
I/O Module Field Installation Guide