Galvin Engineering Haws 8100-A 製品インストール・マニュアリン

TROUBLESHOOTING

PROBLEM
1. No Flow.
2. Insufficient water flow at shower
3. Water does not drain properly.
4. Water leak between joints or fittings.
For more information about GalvinSafe
1.
Check the main shut-off valve.
2. a. Verify minimum 210 kPa flowing supply
line pressure.
b. Probable clogging of flow control
inside shower head. Unscrew shower head
off elbow and clean rubber flow control.
3.
Check your drain system for debris. Check
the main waste line of your building to see
if it does handle the capacity required for
the entire drainage system
4.
Tighten loose connections. If leak persists,
the application of hot water will sometimes
reseat improperly applied joint compound.
After 30 minutes wait and retest. A
persistent leak will necessitate reassembly
and additional sealant.
®