11. Specifications

UNIVERSAL INPUT
Strain Gauge:
Thermocouple
Calibration:
PT100 Calibration:
B
DC Calibration:
Sampling Rate:
Impedance:
Sensor Break
Detection:
Isolation:
Logic Input
Input Signal:
Isolation:
350Ω, by means of 4 or 6 wire (6 to use internal Shunt resistor)
Bridge excitation: 10Vdc ± 7%
Bridge Sensitivity: 1.4-4mV/V
Shunt Value: From 40%to 100%
Input signal Span: -25% to 125% (Approx. -10mV to +50mV)
±0.1% of full range, ±1LSD (±1°C for Thermocouple CJC).
BS4937, NBS125 & IEC584.
±0.1% of full range, ±1LSD.
S1904 & DIN43760 (0.00385
±0.1% of full range, ±1LSD.
10 per second, 16 bit resolution approximately
(100ms sample time)
>10M
resistive, except dc mA (5
Strain Gauge: Depending on user setting InPF can cause input to fail high scale
or low scale reading. Reading will fail on either, Sig+ or Sig- loss, or incorrect
excitation output <0.8mA and >50mA supply.
Thermocouple/RTD: High alarms activate for sensor break. Linear 4 to 20mA,
2 to 10V and 1 to 5V DC: Low alarms activate for sensor break.
Note: Sensor break not detectable on 0 to 20mA, 0 to 50mV, 0 to 5V & 0 to
10v input types.
Isolated from all outputs. Universal input must not be connected
to operator accessible circuits if single relay outputs are
connected to a hazardous voltage source. Supplementary
insulation or input grounding would then be required
If the Logic State setting in Config Mode = CLS, Reset or Tare occurs on an
Open to Closed transition, or high (3 to 5VDC) to low (<0.8VDC) transition.
If Logic State setting in Config Mode = OPN, Reset or Tare occurs on a Closed
to Open transition, or low (<0.8VDC) to high (3 to 5VDC)) transition.
No isolation from inputs and other outputs.
P/N: n/a
www.dynisco.com
/
/°C).
) and V (47k
Rev: n/a
ECO: n/a