- ページ 6

計測機器 AGS CO2-XのPDF インストレーション オペレーション&メンテナンスをオンラインで閲覧またはダウンロードできます。AGS CO2-X 12 ページ。 Carbon dioxide & temperature monitor

Installation, Operation & Maintenance

Configuration Settings

There is a settings switch on the CO2-X board. Switch it on to prompt the on-screen menu. Navigate the menu using
the buttons on the board. When changes have been made – turn the settings switch off.
[SEL.] button
Scroll through functions (highlighted red).
Change the desired setting when highlighted.

Configuration

NAT. -
Natural Ventilation Mode
Pre Alarm: >1300ppm >23 °C/ 73.4°F
Alarm:
>1500ppm >25 °C/ 77.0°F
CO
Pre-alarm relay switch: 1300ppm
2
CO
Alarm relay switch:
2
MECH. -
Mechanical Ventilation Mode (Recommended for buildings with mechanical ventilation).
Pre Alarm: >800ppm >23 °C/ 73.4°F
Alarm:
>1000ppm >25 °C/ 77.0°F
CO
Pre-alarm relay switch: 800ppm
2
CO
Alarm relay switch:
2
KITCH. –
Kitchen/Gas in Use Ventilation Mode (Recommended for kitchen environments).
Pre Alarm: >1500ppm >23 °C/ 73.4°F
Alarm:
>2800ppm >25 °C/ 77.0°F
CO
Pre-alarm relay switch: 2800ppm
2
CO
Alarm relay switch:
2
Rev 5 10-21
0-10V ANALOGUE OUTPUT 1 & OUTPUT 2
These connections are used to regulate external fan speed controllers (supplied
separately). Connect direct to fan speed controllers or via your Merlin panel [0-
10V] terminal if available. Minimum voltage output can be configured in settings
menu from zero to 5 volts.
0-10V output can be driven by the status of current CO
temperature only or by the status of both levels (whichever is greatest).
12-24V (AC or DC) POWER
To power the CO2-X with 12-24v power – this should be supplied to the [12-24V
POWER INPUT] connector (+ / -).
This connection can be either AC or DC.
(
Recommended for buildings without mechanical ventilation).
1500ppm
1000ppm
4500ppm
[OK] button
Highlights setting (red).
Press to save desired setting.
0-10V Analogue Output: Linear Progression.
Min output (1-5V) from 600ppm 23 °C/ 73.4°F
Max output (10V) from 1500ppm 27 °C/ 80.6°F
Boost from: 400 - 1499ppm 0°C/32°F – 26.9°C/ 80.4°F
0-10V Analogue Output: Linear Progression.
Min output (1-5V) from 600ppm 23 °C/ 73.4°F
Max output (10V) from 1000ppm 27 °C/ 80.6°F
Boost from: 400 - 999ppm 0°C/32°F – 26.9°C/ 80.4°F
0-10V Analogue Output: Linear Progression.
Min output (1-5V) from 600ppm
Max output (10V) from 2800ppm 27 °C/ 80.6°F
Boost from: 400 - 2799ppm 0°C/32°F – 26.9°C/ 80.4°F
Buzzer / Mute from: >2800ppm
Merlin CO2-X
level only, by current
2
23 °C/ 73.4°F
6