安全装置 Jade Bird JBE-2101のPDF マニュアルをオンラインで閲覧またはダウンロードできます。Jade Bird JBE-2101 4 ページ。
Overview
JBE-2101 is a conventional manual call point (MCP) designed to be
compatible with a wide range of conventional fire panels and input
modules. This MCP sets an installer-selectable resistive load to the fire loop
when its resettable element is pressed.
After activation, the MCP will remain in alarm until it is reset with the
supplied reset key. There is no glass break element in this device, so the
reset operation is conveniently done without the need to replace any
element.
The JBE-2101 also features a pair of normally open clean (voltage-free)
contacts, which close at activation. These can be optionally used for a local
action or to provide an activation signal to third party systems.
Technical data
Category
Working voltage
Connection
Wire size
Quiescent current
Alarm load
Clean contact rating
Working temp.
Storage temp.
Environment Humidity
Red LED Indication
Dimensions (LxWxH)
IP rating
Weight
Jade Bird Fire Alarm Systems – JadeBird.eu.com
M-2101-1: JBE-2101 Manual Call Point data sheet V1.0
EN 54-11 type A indoor MCP
6-30 V DC
2-wire conventional zone
0.5 – 2.5 mm
2
0 mA
Built-in 680 Ω and 470 Ω + option for external R.
0.1 A / 30 V DC
-10℃ ~ 55℃
-30℃ ~ 75℃
≤ 95% RH (no condensation nor icing)
Steady on when in alarm.
90×90×52 mm
IP40
160 g
1 / 4