3 INTEGRATING THE MAS-1
MAS-1
the current transmitted though the MAS-1. The red wire (see Fig-
ure 2) of the MAS-1 is connected to a voltage output terminal that
is able to supply 12 to 32 VDC. The black wire is connected to an
input terminal that accepts a current input ranging from 4 mA to
20 mA. For the MAS-1 to function properly, the voltage drop from
the red to the black lead must be 12 V or greater.
Figure 2: Typical Wiring Connection
Non-Conventional
When using a device, such as a data logger, that does not have
an input capable of measuring current a pickoff resistor can be used
as shown in figure 3. Assuming that the single ended input has an
input impedance, or resistance, much larger that of R
, then all
V olt
of the current in the 4-20 mA loop passes through R
. If the data
V olt
logger can measure the voltage drop over the R
, then the current
V olt
can be calculated as:
V
measured
I =
(1)
R
V olt
where I (mA) is the 4-20 mA current, R
(ohms) is the resistance
V olt
of the pickoff resistor, and V
(mV) is the voltage drop over
measured
R
.
V olt
6