- ページ 10
水ポンプ Adey CP1-03-04916のPDF 設置およびサービスをオンラインで閲覧またはダウンロードできます。Adey CP1-03-04916 19 ページ。 Digital pressurisation unit
6 .15 Controller overview
The pressurisation unit controller is designed to be intuitive to use and allows
functions and alarms to be set by the installer/user . It also allows faults to be
monitored and logged to enable easier system fault diagnosis .
The functions are set using the 4 buttons (A, B, C & D) on the front of the
controller and with the help of on screen prompts via the back lit LCD display .
On the front of the APU a green 'power on' light will be displayed whilst the
unit is powered . If an alarm or error is raised the red 'Error' light will be
displayed .
A number of pressure set points can be set using the menus, these set points are
detailed below, 1 to 4 and in the description of the function .
HIGH ALARM SET VALUE (1)
SYSTEM PRESSURE SET VALUE (2)
DIFFERENTIAL SET VALUE (3)
LOW ALARM SET VALUE (4)
Fig. 20
SYSTEM FILL MODE
Fig. 21
Button A Scrolls up through menus or increases set values .
Button B Enters menus or selects values .
Button C Scrolls down through menus or reduces set values .
Button D Returns to previous menu
PUMP 'OFF'
PUMP 'ON'
TIME
NORMAL OPERATION
A
B
C
D
- 18 -
6 .16 Function list & explanation
The functions are contained within an initial display and 3 menus:-
Setting menu (pass code protected) see Section 6 .18 .
Advanced setting menu (pass code protected) see Section 6 .19 .
Test menu (pass code protected) see Section 6 .20 .
6 .17 Initial display
On start up, and during operation, if the APU has had no button inputs for
1 minute, a home screen (see Section 7 .11) will be displayed with system
pressure, tank water level, any active alarm and any pump that is operating at
the time . By using buttons A & C to scroll up or down the following screens will be
displayed:-
System pressure
Active errors
System fill status
Pump activity
Pump run time
Alarm reset
6 .18 Setting menu
(Pass code protected, if set)
The following functions can be set and modified:-
Sets the required system pressure.
System pressure (2)
to the maximum set value for the pressurisation unit model - Midi 130
see Fig . 20
& 230 - 3 .5 bar max; Midi 150 & 250 - 4 .1 bar max .
Sets the pressure at which the pressurisation unit will turn
Differential pressure (3)
on at as the system pressure falls. Relative to the system
see Fig . 20
pressure.
cannot be set above 0 .1 bar below the System pressure (2) .
Sets high system pressure alarm.
Hi Alarm (1)
above the System pressure (2) . Cannot be set below System pressure
see Fig . 20
+ 00 .5 bar . Alarm auto resets when system pressure is reduced below
alarm level .
Sets low system pressure alarm.
Lo Alarm (4)
below the System pressure (2) - Differential pressure (3) - 0 . 0 5 bar .
see Fig . 20
Alarm auto resets when system pressure is increased above alarm
level
Turns on system fill option
the System pressure (2) has been reached or a period of 24 hours has
System fill
passed since it was set to 'on' . Lo alarm and Max runtime functions
are disabled whilst System fill is turned on . Pumps will stop if the
System pressure (2) or Hi alarm pressure (1) is reached .
Alarm triggered if the APU starts more than the preset
Start Activity High
limit in 24 Hours.
Set to minimum of 100 starts per 24 hrs . Set in increments of 100 .
Set in 0 .1 bar increments up
Set in 0 . 0 5 bar increments below the System pressure (2),
Set in 0 . 0 5 bar increments
Set in 0 . 0 5 bar increments
. System fill option will turn off once
- 19 -