ODGSR Series Outdoor Gas Fireplace
Nailing
Flange
FP1416
Fig. 8 Parts identification.
FP1416
ODUVSR
part id
11/24/03 djt
Nailing Flange
Fig. 9 Exterior chase installation.
FP1416
ODUVSR
part id
11/24/03 djt
8
*Do not install
header until unit
is in place.
Standoff
Surround
Gas
Line Ac-
cess
Screen
Grate
Firebox
Valve Access Panel
Interior sides of an exterior chase
should be weather proof
*Do not install
header until unit
is in place.
Standoff
Surround
Gas
Line
Access
Screen
Grate
Firebox
Valve Access Panel
FP1644
Gas Line Installation
This appliance must be isolated from the gas supply
piping system by closing its individual manual shut off
valve during any pressure equal to or less than 1/2 psig
(3.45 kPa).
The appliance and its individual shutoff valve must be
disconnected from the gas supply piping system during
any pressure testing of that system at test pressures in
excess of 1/2 psig (3.45 kPa).
If gas piping from the source to the appliance location
has not been accomplished, install the required pipe.
Consult local plumbing code to assure proper pipe size.
The gas pipeline can be brought in through the right
side of the appliance. A knockout is provided to allow
for the gas pipe installation and testing of any gas con-
nection.
NOTE: The gas line connection can be made with 3/8"
copper tubing approved for propane or natural gas, 1/2"
rigid pipe or an approved flex connector, then reduced
to 3/8" to the appliance. Because some municipalities
have some additional local codes, it is always best to
consult your local authority.
U.S.: Consult the current National Fuel Gas Code, ANSI
Z223.1/NFPA 54.
Canada: CSA - B149.1 installation code.
Test for leaks. Use a 50/50 solution of liquid soap and
water to test for leaks at gas fittings and joints. Apply
water/soap solution with brush only - do not over apply.
NEVER test with an open flame.
The gas control is equipped with a captured screw type
pressure test point, therefore it is not necessary to pro-
vide a 1/8" test point up stream of the control.
When using copper or flex connector use only approved
fittings. Always provide a union so that gas line can
be easily disconnected for burner or fan servicing.
See gas specification for pressure details and ratings.
NOTE: If flex connector is used, it must be kept inside
of the appliance. (Fig. 10)
1/2" Gas Supply
1/2" x 3/8" Shut-off Valve
FP598
Fig. 10 Typical gas supply installation.
GF598
nvb GAS SUPPLY INSTALL
12/4/97
3/8" Nipple
3/8" Union
3/8" Nipple