Installation
• Every device must have its own flue with a
diameter equal to or larger than the stove's
smoke clearing tube and a height not less than
that declared.
• Never use two stoves, a chimney and a stove,
a stove and a wooden kitchen, etc. in the same
environment, since the draught of one could
damage the draught of the other.
• Collective type ventilation ducts that can lower
the atmospheric pressure in the installation
environment are not permitted, even if installed
in environments that are adjacent to and
communicating with the locale of the installation.
• It is forbidden to make fixed or mobile
openings in the flue to connect devices different
from that for which it is originally intended.
• It is forbidden to pass other air feeding
channels or tubes for the use of the electrical
system through the flue, even if they are of a
larger size.
• It is recommended for the flue to be furnished
with a chamber which collects solid material and
possible condensation situated below the
vertical entrance to the flue so that it can be
easily opened and inspected through the
air-tight door.
• Whenever flues with parallel exits are used it is
advisable to raise the upwind chamber by one
element.
• The chimney tube must never pass across a
combustible surface.
The Chimney Cap:
The chimney cap must meet the following
requirements:
• It must have the equivalent diameter and
internal form of the flue.
• It must have a useful outlet diameter of not
less than double that of the flue.
• The chimney cap on the roof or that remains
in contact with the outside (for example, in the
case of open lofts or attics), must be covered
with elements in brick or tile and must, in all
cases, be well insulated.
• It must be constructed to prevent rain, snow,
and extraneous bodies from entering the flue
and so that the discharge of the products of
combustion is not inhibited by wind from any
quarter or of whatever strength (wind-proof
chimney cap).
• The chimney cap must be positioned in such a
way as to guarantee the adequate dispersion and
dilution of the products of combustion and, in all
cases, must be out of the reflux zone. This zone
has different dimensions and forms according to
the angle of inclination of the roof so it is
necessary to adopt minimum heights (Fig. 2).
• The chimney cap must be a wind-proof type
and must be above the ridge.
• Eventual structures or other obstacles that are
higher than the chimney cap must not be too
close to the chimney cap itself.
Figure 2. Characteristic of chimney cap
YES
NO
4