- ページ 7
暖房システム Airflow Uno habのPDF 取付キットをオンラインで閲覧またはダウンロードできます。Airflow Uno hab 16 ページ。 Cavity wall decentralised mechanical ventilation with heat recovery unit
Airflow Uno hab にも: 据付・取扱説明書 (16 ページ), 使用方法 (2 ページ), メンテナンス・マニュアル (2 ページ)
CHAPTER 4
UNIT OVERVIEW
© Airflow - we reserve the right to make changes without prior notice
4.0
Unohab Cavity Wall Installation Kit - exploded view
4.1
Technical data
Unit
Fan speed
Air flow supply/extract rate
[m
/h]
3
Air flow supply or extract rate
[l/s]
Sound pressure level LPA dB(A)
Sound insulation Dn,e,w dB
Power consumption [W]
Heat recovery efficiency
Power supply
Rated current [mA]
Protection class
El. power supply cable
El. power supply cable (controller)
El. power supply cable (fan unit)
Connection according to wiring diagram no.
Weight approx. [kg]
Working range temperature
4.2
Dimensions
Room Supply / Extract
All dimensions in mm
4.3
Accessories
Further accessories and suitable system components, such as switching power supplies, extractor fan module,
casing for controller surface mounting, are available within the Unohab range. Details can be found in the
Unohab brochure and on the website at airflow.com
Unohab Cavity Wall Installation Kit
Unohab
1*
2**
3*
24
14
32
3.8
6.6
8.8
21
14
27
44
1 .6
2.1
2 .8
up to 88%
Input 230V~ 50/60Hz / Output 12VDC
21
17
27
IP20
NYM-O 2 x 1.5mm
NYM-O 2 x 1.5mm
J-Y (ST) Y 3 x 0.8mm
SD-3 / SD-4
2.8
-12°C up to +40°C
8
Wall sleeve ø 160
(Core hole ≥ ø 162 with outward gradient)
(Core hole ≥ ø 172 horizontal)
7
Installation and Operating Instructions
*Default fan speeds
4**
5*
**Fan speeds, which can be also selected in
Duplexvent Unohab software. In total only three
37
45
fan speeds can be selected at the same time.
10.2
12.5
29
34
3.4
4 .5
32
42
2
2
2
fig.2