II. MOUNTING INSTRUCTIONS (General)
INDOOR MOUNTING ONLY -
To achieve optimum protection, the air curtain should be
mounted on the inside of the building, flush to the wall and
as close to the top of the door opening as possible. To ensure
peak performance, keep the air stream free of obstructions.
The air curtain will not perform properly if negative air
pressure exists in the building. Under these conditions,
a means for makeup air to the building must be provided
so that the air pressure on both sides of the opening is in
balance.
Before mounting the air curtain, check the supporting structure
to verify that it has sufficient load-carrying capacity to support
the weight of the air curtain(s). The mounting hardware
(supplied by others) should be capable of supporting a
minimum of three (3) times the weight of the air curtain.
See Table 1.
IMPORTANT: A minimum of 4" is required above the top rear
corner of the air curtain for the installation and removal of the
inlet screen, and to ensure proper airflow.
A.
When determining the mounting location for the air
curtain(s), make sure that nothing interferes with the
curtain of air developed when the discharge vanes
are directed from 0° to 20° toward the door opening. If
the air stream strikes any obstruction (the top edge of the
doorway, a door opening device, etc.), the effectiveness
of the air curtain will be greatly reduced. See Figure 2.
B.
For optimum performance, the bottom of the air curtain
(discharge nozzle) should be no more than 1" above
the top of the door opening with the air curtain(s)
mounted flush to the wall. If the air curtain must be
mounted higher, it must be spaced out from the
wall 3/8" for every inch the air curtain is above the door
opening. See Figure 3. For optimum protection, any void
between the air curtain and the wall should be sealed
along the full length of the air curtain.
C.
Do not block (obstruct) the air intake screen. Insufficient
airflow can cause the unit to overheat.
D.
The air curtain(s) shall:
1.
Have a minimum clearance of at least 4"
from the sides and 4" from the top.
2.
Have a minimum clearance of at least 6'
between the bottom of the air curtain and the floor.
3.
Be installed Indoors Only.
Proceed to either Section III - WALL MOUNTING or
E.
Section IV - SUSPENDED MOUNTING
III. WALL MOUNTING
PREPARATION
A.
1.
Locate the wall mounting plates, in the carton that
contained the unit. See Figure 4. For units over 72",
there are more than two wall mounting plates.
2.
Use ¼"-20 bolts to attach the wall mounting plates
to the back of the air curtain.
4" minimum
side & top
clearance from
combustible
material
20°
EXTERIOR
Figure 2 - General Mounting
Net Weight
MODEL
AI10
AI10
AI10
Amb.
Elec.
Steam
AI10-E-1036
85
88
110
AI10-E-1042
94
97
122
AI10-E-1048 110
113
141
AI10-E-1060 119
122
156
AI10-E-2072 170
176
216
AI10-E-2084 188
194
240
AI10-E-2096 220
226
278
AI10-E-2108 229
235
293
AI10-E-2120 238
244
306
AI10-E-3132 305
314
384
AI10-E-3144 330
339
415
TABLE 1 - Weight Chart
Figure 3 - Wall Mounting Location
-4-
Discharge
Nozzle
6' minimum
INTERIOR
Airstream
Net Weight
AI10
MODEL
AI08
AI08
AI08
Hot
Amb.
Elec.
Steam
Water
AI08-E-1036
107
48
53
119
AI08-E-1042
53
58
AI08-E-1048
138
58
63
AI08-E-1060
153
69
74
AI08-E-1072
210
79
89
AI08-E-2084
234
106 116
AI08-E-2096
272
116 126
AI08-E-2108
287
127 137
AI08-E-2120
300
138 148
375
406
AI08
Hot
Water
68
68
76
75
83
83
99
99
117
117
149
149
164
164
180
180
196
196