Original Issue Date: 11/09
Model: 5/7.5/10EKD and 4/6/8EFKD
Market: Marine
Subject: Siphon Break Kit GM60007-KP1 for Sound Shielded Units
Introduction
Use these instructions to install a siphon break on
sound-shielded generator sets.
prevents seawater entry into the generator set engine
when the engine exhaust manifold outlet is less than
230 mm (9 in.) above the waterline of a fully loaded
docked or stationary craft.
Read the entire installation procedure. Perform the
steps in the order shown.
Note: Install this siphon break kit on generator sets
equipped with the sound shield kits specified in
Figure 1. Do not install these siphon break kits on
generator sets without sound shields.
Model
5EKD/4EFKD
7.5EKD/6EFKD
10EKD/8EFKD
Figure 1 Sound Shield Kits

Safety Precautions

WARNING
Accidental starting.
Can cause severe injury or death.
Disconnect the battery cables before
working
on
Remove the negative (--) lead first
when disconnecting the battery.
Reconnect the negative (--) lead last
when reconnecting the battery.

INSTALLATION INSTRUCTIONS

A siphon break
Factory
Field
Installed Kit
Installed Kit
GM55219-KA1 GM55219-KP1
GM55219-KA2 GM55219-KP2
the
generator
set.
Disabling the generator set.
cause severe injury or death.
generator set or connected equipment, disable the generator
set as follows: (1) Move the generator set master switch to the
OFF position. (2) Disconnect the power to the battery charger.
(3) Remove the battery cables, negative (--) lead first.
Reconnect the negative (--) lead last when reconnecting the
battery. Follow these precautions to prevent starting of the
generator set by an automatic transfer switch, remote
start/stop switch, or engine start command from a remote
computer.
WARNING
Hazardous voltage.
Can cause severe injury or death.
Operate the generator set only when
all guards and electrical enclosures
are in place.
Servicing the generator set when it is operating. Exposed
moving parts can cause severe injury or death. Keep
hands, feet, hair, clothing, and test leads away from the belts
and pulleys when the generator set is running. Replace
guards, screens, and covers before operating the generator
set.

Installation Procedure

1.
Remove the generator set from service.
1.1
Press the start/stop button to stop the generator
set. The engine stops.
1.2
Press the power button to turn off the controller.
1.3
Disconnect the power to the battery charger, if
equipped.
1.4
Disconnect the generator set engine starting
battery, the negative (--) lead first.
TT-1509
4/14a
Accidental starting can
Before working on the
Moving parts.