Screen Four: SET THRESHOLD TOTAL 2 (factory set at 80)
Set this option for the total amount of gallons required to deliver a
service call alert to the customer
 Set threshold gallons (x1000)
Recommended setting for 9x48 system is 80; 10x54 system is120
 Yellow light blinks at 80% threshold
 Red light blinks at 90% threshold
 Alarm beeps at 100% threshold
 Opt2 connection is powered with 12 VAC at 100% threshold
(30 milliamps (mA) max.)
 Press the Flow button to advance to next screen
Screen Five: SET GAL/MIN (no factory setting)
This function is primarily for an external device, i.e. a secondary pump,
chemical feed or auxiliary signal, etc
 Set GPM for the 20 mA output flow rate
 Zero flow is a fixed 4 mA output
 Verify polarity 4-20 mA output at J2 connection
 4-20 mA proportional flow rate output
 Press the Flow button to advance to next screen
Screen Six: SET GAL 1 (factory set at 20)
This setting fixes the number of gallons before auto pump starts
 Set the gallon batch to energize Opt1 connection
 Set at 10 gallons
For Air Pump factory setting is 20 gal
Feed Pump setting is 1 gal. for 10 GPM peak flow; 2 gal. for 20 GPM
peak flow; 3 gal. for 30 GPM peak flow; 4 gal. for 40 GPM peak flow
 A setting of zero energizes Opt1 like a flow switch, sensitive at .5 GPM
 Press the Flow button to advance to next screen
Screen Seven: SET MIN 1
This setting factors the run time duration of the auto air pump or
feed pump after water usage has discontinued (.1 would be 6 seconds.)
 Set delay off in minutes for Air Pump - Opt1 connection
 Set between 0.1 and 90 minutes.
Air Pump setting is .33min
Feed pump setting is 0.10 min.
 Opt1 is 12 VAC (30 mA max.)
 Press the Flow button to advance to next screen
*Please contact your water professional to confirm the proper settings for your application. The above values are recommendations