- ページ 29

エンジン Kohler 4EFのPDF オペレーションをオンラインで閲覧またはダウンロードできます。Kohler 4EF 48 ページ。 Marine generator sets

Kohler 4EF オペレーション
1
22
Waterline
21
1. Mounting base
2. Retaining cap
3. Reed valve assembly
4. Silencer vertical lift 1.2 m (4 ft.) max.
5. Exhaust mixer elbow distance above waterline. If less than
23 cm (9 in.), siphon break is required.
6. Siphon break distance above waterline 30.5 cm (1 ft.) min.
7. Siphon break
8. Exhaust mixer elbow
9. Heat exchanger (locations vary by model)
10. Coolant recovery tank
11. Locate coolant recovery tank at same height as heat exchanger
Figure 3-9 Siphon Break (Plastic "U" Type) Installation
Note: Consult the installation manual for complete
explanation of dimensions and other installation
considerations.
TP-5985 10/02
2
3
6
5
4
20
19
18
7
8
16
17
12. Seawater strainer
13. Seacock
14. Intake strainer
15. Engine-driven seawater pump
16. Exhaust hose pitch 1.3 cm per 30.5 cm (0.5 in. per ft.) min.
17. Water lock (optional)
18. Silencer distance from exhaust mixer elbow 3 m (10 ft.) max.
19. Silencer (customer-supplied)
20. Exhaust hose pitch 1.3 cm per 30.5 cm (0.5 in. per ft.) min.
21. Exhaust outlet distance above waterline 10 cm (4 in.) min.
22. Seawater outlet
Section 3 Scheduled Maintenance
9
10
11
12
15
13
14
TP-5586-3
17