1.8.3
Field-Connection Terminal Block
The generator set is equipped with a field-connection
terminal block located in the air inlet area near the
junction box. Leads have been factory-installed from
the junction box to the terminal block for easy field
wiring.
See the dimension drawing in Section 1.5 for the
terminal block location. See Figure 1-19 or Figure 1-20
for terminal block details. Refer to the terminal block
decal for connections and cable sizes. Also see
Section 2, Wiring Diagrams.
Note: The connections on the revised terminal block
are arranged in a different order than the original.
Be sure to follow the connections shown on the
decal on the generator set.
Route AC leads through flexible conduit. Ensure that
the leads and conduit do not interfere with the operation
of the generator set or obstruct the service areas. Route
low-voltage communication leads through separate
conduit.
1. Field-connection terminal block
2. Decal
Figure 1-19 Original Field-Connection Terminal Block
TP-6733 8/11
Procedure
1
2
GM66565
Figure 1-20 Revised Terminal Block
1. Drill holes for the conduit fittings.
Figure 1-17 and Appendix B for the recommended
electrical inlet locations. Feed the cables through
the openings.
2. Connect the leads from the transfer switch
emergency source lugs to the L1 and L2
connections on the generator set terminal block.
3. Connect the neutral (L0) and ground (GRD) leads
from the ATS and the main panel to the
corresponding connection points on the terminal
block. See Section 1.8.4, Grounding.
1. Terminal block
2. Decal
See the
1
2
GM80177
Section 1 Installation
23