1.1 General
Have an authorized distributor/dealer install the
generator set outdoors according to the instructions in
this manual. Do not install this generator set indoors.
Use the specifications provided here only in the initial
planning. Use the generator set and transfer switch
dimension drawings and wiring diagrams for installation.
1.2 Lifting
WARNING
Unbalanced weight.
Improper lifting can cause severe
injury or death and equipment
damage.
Do not use lifting eyes.
Lift the generator set using lifting bars
inserted through the lifting holes on
the skid.
Model
14RES/RESL
20RES/RESL
Figure 1-1 Approximate Weights
Approximate generator set weights are shown in
Figure 1-1. Use lifting bars inserted through the holes in
the skid to lift the unit. See the dimension drawings on
the following pages for lifting hole locations.
TP-6733 8/11
Weight, kg (lb.)
186 (410)
227 (500)
Section 1 Installation
1.3 Generator Set Inspection
Complete a thorough inspection of the generator set.
Check for the following:
1. Inspect the generator set for loose or damaged
parts or wires. Repair or tighten any loose parts
before installation.
2. Check the engine oil. Fill, if necessary, with the
recommended viscosity and grade of oil. Use
synthetic oil, API (American Petroleum Institute)
Service Class SG or higher.
Operation Manual, for additional information.
1.4 Location and Mounting
See the dimension drawings on the following pages for
the generator set dimensions and fuel and electric inlet
locations.
The drawing dimensions are shown in
millimeters, with inches in brackets.
Install the generator set outdoors. Provide the minimum
clearance around the generator set shown in the
clearance drawings on the following pages. Locate the
generator set so that the hot exhaust does not blow on
plants or other combustible materials. Do not install the
generator set where exhaust gas could accumulate and
seep inside or be drawn into a potentially occupied
building.
1.4.1
Exhaust Requirements
WARNING
Carbon monoxide.
Can
cause
fainting, or death.
The
exhaust
leakproof and routinely inspected.
Generator set operation. Carbon monoxide can cause
severe nausea, fainting, or death. Carbon monoxide is an
odorless, colorless, tasteless, nonirritating gas that can cause
death if inhaled for even a short time. Avoid breathing exhaust
fumes when working on or near the generator set. Never
operate the generator set inside a building. Never operate the
generator set where exhaust gas could seep inside or be
drawn into a potentially occupied building through windows, air
intake vents, or other openings.
See TP-6734,
severe
nausea,
system
must
be
Section 1 Installation
11