- ページ 12
プールヒーター Aqua Comfort AC150のPDF オーナーズマニュアルをオンラインで閲覧またはダウンロードできます。Aqua Comfort AC150 12 ページ。
"LP" (Compressor Low Pressure)
• Evaporator coil dirty.
• Fan motor not running.
• Low refrigerant pressure.
• Defective low-pressure switch.
"dPO" Evaporator temperature sensor connection opened. Check for cut or loose sensor wiring or
defective sensor.
"PO" Water temperature sensor connection opened. Check for cut or loose sensor wiring or defective
sensor.
"dPC" Evaporator temperature sensor connection shorted. Check for a short in sensor wiring or
defective sensor.
"Pc" Water temperature sensor connection shorted. Check for a short in sensor wiring or defective
sensor.
"FS" Heat pump in defrost cycle.
"PLE or CSE" EEPROM memory data loss. Hold down the SELECT key until the error message
disappears. The control will be reinitiated to factory default. Re-enter the setpoints.
"SPi" Defective controller, remove power and restart. If error is still present, replace controller.
CALLING FOR SERVICE
• Please eliminate any water flow problems before calling for service.
• If you are unable to contact the installing agent, please go to
contact AQUA COMFORT TECHNOLOGIES,
LLC. A factory representative will assist you or your serviceman over the phone.
SERVICE PERFORMED WITHIN THE WARRANTY PERIOD MUST BE APPROVED BY AQUA COMFORT TECHNOLOGIES,
LLC PRIOR TO SERVICE BEING PERFORMED AND ONLY BY AN AQUA COMFORT TECHNOLOGIES, LLC AUTHORIZED
TECHNICIAN. SEE WARRANTY FOR DETAILS.
Please have the following ready before calling:
IN-GROUND MODEL #:
SERIAL #:
DATE OF INSTALLATION:
NAME OF OWNER:
ADDRESS:
CONTACT #:
www.aquacomfort.com/service-and-support
12
to