- ページ 3
消火器 A.B.S. FIREKILL 15226のPDF 技術データをオンラインで閲覧またはダウンロードできます。A.B.S. FIREKILL 15226 3 ページ。 1-3-6-9-12 kg powder abc
Technical Bulletin
ACCESSORIES ON REQUEST FIREKILL SYSTEMS
On request the firekill system can be electrically activated with automatical detection system.
In the scheme below you can see an example of automatical detection system for firekill system with all its options available
SIGN
LIGHTENING
BOX
Electric actuator (cod. 43001)
It can be connected with an emergency control push button or
through a control panel in case there is an automatic detection
system.
The electric actuator is a pyrotechnical charge, 5 years guaranteed
at a work temperature from -20°C up to +80°C and humidity of
100%. The pyrotechnical charge can work with minimum 12 V
tension and 1 A current.
Code 43001
TEMPETATURE DETECTOR (cod. 47038 - 47019)
The apparatus consists of two contacts mounted on two curved
strips of nickel-iron, the contacts are electronically isolated from
the strips, however, a complex that is called "crew" is in turn
mounted in stress conditions in a sheath consisting of a tube
extruded AISI. The temperature at which the sheath is taken. Any
change in temperature dilates the sheath, which thus increases the
tension that it exerts on the plate, swithing the contact, as
appropriate.
MINIBEND (cod. 28053)
MINIBEND FOR COPPER AND ALUMINUM PIPE FOR EXT.
Ø 8 - 10 - 12 mm IDEAL TO BEND FIREKILL PIPES
Code 28053
Lombardia Street 310, 20861 S.Dam. Brugherio
Tel. +39 - 039 - 839631 - Fax. +39 - 039 - 8396349
1370
e-mail:[email protected]
Code 47038
preset at 141°C
Code 47019
preset at 68°C
DATI TECNICI - Technical Data :
Temp. di intervento – Alarm Temeperature:
Temp. ambiente – Ambient Temperature:
Materiale Conduttori - Conductors material:
Resistenza Conduttori Conductors resistance:
Tensione di lavoro Operatine Voltage:
Materiale isolamento - Insulation material:
Guaina esterna – Outer Jacket
Diametro cavo- Overall cable dia.:
Approvazione - Approval:
Technical data are subject to modification
for improvements without prior notice
a.b.s. S.r.l. (Milan) Italy
www.absfire.it
Capital euro 2,000,000.00
Code 23023
MARINE CONTROL BOX (cod. 23023)
The central unit and control unit are manufactured with materials
immunes to the marine environment and supplied in IP65 version.
Furthermore, the chassis ensures adequate heat dissipation
which allows long periods of operation. It controls all the above
illustrated device. It can be programmed in 4 languages.
Central unit CPU
CONTROL BOX (cod. 23022 or 23022_1)
This unit is used in combination with Firekill extinguishing system for
boat engine or electrical board.
Led green indicates that circuit is operative
Red light indicates that extinguisher has been discharged.
Alarm audible buzzer included in the units will sound when system
has been activated. Remove safety pin, open door, press red button
inside to activate discharge.
Control Box
Cod.23022
180° C - 356° F
max. 105° C (221 ° F)
Acciaio – Steel.
~0,66 KΩ/Km
42Vdc, 30Vac max.
T ermosensibile- Heat sensing
EPC
~
4mm
UL, FM
Fire Extinguisher
Code 23023
Dash board
remote unit
Control Box
Cod.23022_1
THEMOSENSIBLE CABLE
Data Sheet
Code
Date
Check
15241
22/02/15
JC
Rev
Pag.
5
3/3
/AL