- ページ 13
ヒートポンプ Allied 4SHP16のPDF 取付説明書をオンラインで閲覧またはダウンロードできます。Allied 4SHP16 19 ページ。 Single stage heat pump
Before final adjustment is made to the refrigerant charge,
it is imperative that proper indoor airflow be established.
Airflow will be higher across a dry coil versus a wet coil.
Blower charts are calculated with a dry or wet coil basis.
Recommended airflow is 350-450 CFM per ton (12,000
Btuh) through a wet coil. Refer to indoor unit instructions for
methods of determining air flow and blower performance.
The optimum method for checking the charge is by
weight. However the following methods may be used
to confirm the proper charge:
Cooling Mode
1. Operate unit a minimum of 10 minutes before checking
charge.
2.
Measure liquid service valve pressure by attaching an
accurate gage to service port. Determine saturation
temp. from T/P chart.
3.
Measure liquid line temperature by attaching an
accurate thermistor type or electronic thermometer to
liquid line near outdoor coil.
4.
Calculate subcooling (saturation temp. measured
temp.) and compare with table on back of central box
cover.
5.
Add refrigerant if subcooling is lower than table.
Recover refrigerant if subcooling is high.
6.
If ambient temp is lower than 60°F, check charge in
heating mode or weigh refrigerant according to name
plate data.
Heating Mode
Check charge in heating mode if ambient temp is below
60° F. Indoor temp must be between 65° and 75° F.
Follow steps (1) to (6) above and compare with heating
mode subcooling range on the table on back of central box
cover.
Charge must be rechecked again during the cooling
season.
Cold Weather Application
A cold weather accessory kit may be required for heat
pumps operating at ambient conditions below 25°F.
Supplemental heat should be provided for these conditions.
507919-01F
Operation
Demand Defrost System Description
The demand defrost controller measures differential
temperatures to detect when the system is performing
poorly because of ice build-up on the outdoor coil. The
controller "self-calibrates" when the defrost system starts
and after each system defrost cycle. The defrost control
board components are shown below.
The control monitors ambient temperature, outdoor coil
temperature, and total run time to determine when a
defrost cycle is required. The coil temperature probe is
designed with a spring clip to allow mounting to the outside
coil tubing. The location of the coil sensor is important for
proper defrost operation.
NOTE: The demand defrost board accurately measures
the performance of the system as frost accumulates on the
outdoor coil. This typically will translate into longer running
time between defrost cycles as more frost accumulates on
the outdoor coil before the board initiates defrost cycles.
Diagnostic LEDs
See offset control board diagnostic LED table (Table 3) to
determine operational conditions and diagnose problems.
Figure 6. Control Board
Issue 1846
Page 13 of 19