Electrical Connections
Wiring must conform to local codes and NEC/CEC. Refer
closely to wiring diagram in this instruction and the
following information: If electric heat assembly is being
installed in an existing unit, a change in power supply
wiring and disconnect switch may be required. Remove
the original supply wires or disconnect at power source.
Refer to heater nameplate for minimum circuit ampacity
and maximum fuse size.
1- Review heater installed nameplate for MCA values
and enlarge power entry knockouts as needed. Refer
to figure 7 for field wiring.
2- Identify harnesses by markings on the end of wires.
For wiring between F4 and TB2, use the longer
J2 HARNESS
PROVIDED IN KIT
J2 / P2 JACK PLUG CONNECTIONS
J2
P2
P2 ELECTRIC
HEAT HARNESS
FIGURE 4
Page 5
harness provided in the SPPS kit. For wiring between
F4 and TB13, use the shorter harness provided in the
SPPS kit. For power wiring between TB2 and TB3 (or
second power supply wiring to TB3), use the
approximately 8-foot harness provided in the electric
heat kit. See figure 3 for harness routing.
3- Locate J2 low voltage harness in the electric heat kit.
Connect J2 to P2 electric heat plug. See figure 4.
Route wires on other end of harness to the control
panel. Use the smaller knockout in the bottom of the
control panel.
4- Make J2 harness connections in the control box as
shown in figure 5.
5- Select wiring diagram with appropriate voltage and
affix to unit in location shown in figure 6.