Parameter Name
Default Value
For Channel 3 (Microwave Sensor)
Local Code
1
Sub Local Code
Not set
Area Code(s)
Not set
Sensitivity On
5
Sensitivity Off
5
Walk Test LED
Off
Lux on level
400
(Switch level on)
Lux off level
700
(Switch level off)
Power Up State
On
Disable Detector
N
Range / Options
Description
1 to 999
A number corresponding to the Local Code of all devices to be
controlled by this Microwave input channel.
1 to 99
A number corresponding to the Sub Local Code of all devices to be
controlled by this Microwave input channel.
1 to 999
A number corresponding to the Area Code of all devices to be controlled
0 to clear
by this Microwave input channel. Up to 10 Area Codes can be set for
Channel 3.
1 (min) to 9 (max) Sensitivity level for detecting movement when the detector is already on.
*UHS4 sets Sensitivity On and Off to the same value.
1 (min) to 9 (max) Sensitivity level for detecting movement when the detector is off.
sets Sensitivity On and Off to the same value.
On or Off
When set to On this causes a red LED to flash on the sensor when it
detects movement. Use this feature to check for adequate Sensitivity
On/Off levels.
0 (disabled) or
Sets a minimum light level below which the Microwave sensor is
1 to 999
enabled, allowing lights to be turned on by movement.
0 (disabled) or
Sets a maximum light level above which the Microwave sensor is
1 to 999
disabled, preventing lights from being turned on by movement.
On or Off
When power is applied to the unit the Microwave sensor goes through a
settling down period of up to 40 seconds. With Power Up set to On, the
outputs go to the last levels for up to 15 seconds, then the Local On
Scene (scene 1 by default) is invoked plus the Time Adjustment Period,
after which the Local Step/Off Scene (scene 20 by default) is invoked
(assuming no movement is detected). With Power Up set to Off, the
outputs go to the last levels until movement is detected.
Y or N
Disables detection, leaving the relay output permanently off with the
dimming output operational. This mode is used when the unit is for
maintained illuminance only.