7. Ch2 (dim) set Menu

Use this menu for programming Channel 2. This is the dimmed channel.
IR cmd
Light lev
Light level. Maintained illuminance level (adjustable between 1 and 999). At 999 the
output will be always be at maximum.
Presence
Auto switch on with detection, auto off after movement ceases and time delay ends.
Absence
Manual switch on, auto off after movement ceases and time delay ends.
Sw lev on
Lux level setting to prevent the luminaires being switched on if the ambient light level is
sufficient (adjustable between 1 and 9). The luminaires will always be switched on at
level 9. For a higher resolution of „switch level on‟ a scale of 101-199 is available in the
„Special menu‟.
Sw lev off
Lux level setting to switch the luminaires off during occupancy if the ambient light level
goes above the setting (adjustable between 1 and 9). Level 9 will always keep the lights
on. This setting can be used for "window row switching". For a higher resolution of
„switch level on‟ a scale of 101-199 is available in the „Special menu‟.
DSI
Selects DSI dimming
DALI
Selects DALI dimming
Memorise
If this is set to Yes, the last manual lux level set will be memorised and used as the new
switch on level.
On value
Dimming output level when switched on (0-99).
Off value
Dimming output level when switched off (0-99). If a non-zero off value is set, then the
output will toggle between this value and completely off depending on the switch level
on and off values. For example, if it is light outside, the fittings will be off if there is no
occupancy. If it is dark outside, they will adopt the preset off value. This feature is only
enabled if „Min value‟ is set to 99.
Fade value
After occupancy ceases, this dimming output level is loaded for the fade time
(adjustable between 0 and 99).
Fade mins
This is the time period (adjustable between 0 and 99 minutes) that the luminaire will be
held at the fade value before turning off. A value of 0 disables the fade function.
Max value
Maximum dimming output level (adjustable between 0 and 99).
Min value
Minimum dimming output level (adjustable between 0 and 99).
Burn-n hrs
Determines how long the output will be at 100% so that lamps „burn-in‟ (adjustable
between 1 and 999 hours). The ‟burn-in‟ time is not affected by power supply interrup-
tions. To disable burn-in set to 0 .
Speed on
Determines the dimming response speed after the setup time has finished. Measured in
0.1 sec intervals.
Speed set
Determines the dimming response speed during the set up time. Measured in 0.1 sec
intervals.
Set secs
Determines how long the dimming response set-up period lasts on power-up or on
setting change (adjustable between 1 and 999 seconds). This enables the desired lux
level to be achieved rapidly when the lights come on, or during setup.
Special
Selects the special menu below
6
Description
Default
Products
-DD & MWS7
only
Product
-DD & MWS7
dependant
only
Product
-DD & MWS7
dependant
only
9
-DD & MWS7
only
9
-DD & MWS7
only
Default
-DD & MWS7
only
-DD & MWS7
only
N
-DD & MWS7
only
99
-DD & MWS7
only
0
-DD & MWS7
only
10
-DD & MWS7
only
0
-DD & MWS7
only
99
-DD & MWS7
only
1
-DD & MWS7
only
0
-DD & MWS7
only
40
-DD & MWS7
only
5
-DD & MWS7
only
120
-DD & MWS7
only
-DD & MWS7
only