Installing the SS-100
for Einstein Control-
lers
Figure 2-1 - Unit Detail
1.
Mount the SS-100 near the appropriate Ein-
stein controller. As in the case of a modem,
the SS-100 will be connected to the Einstein
controller that is designated as the site alarm
annunciator (See Section 2.1.).
2.
Obtain a straight through serial cable with a
male DB25 (25-pin) connector on one end
and a female DB9 (9-pin) connector on the
other end. (An appropriate serial cable is in-
cluded with the kit).
3.
Attach the DB25 connector end of the serial
cable to the SS-100 serial port and attach the
DB9 end to the Einstein.
Figure 2-2 - Wiring Example
4.
Connect one end of a twisted-pair Ethernet
8 • Configuring the SS-100 for Einstein Controllers
cable to the RJ45 connector on the SS-100.
The other end of this cable is attached to
equipment (hub or router) that provides con-
nectivity to the LAN.
5.
Attach one end of the supplied SS-100 power
cable to the SS-100 and plug the other end
into a wall outlet (120VAC). There is no
power switch on the SS-100.
6.
Before the initial configuration of the SS-
100, reset it to the factory default configura-
tion. This is done by holding in the reset but-
ton (with a straightened paper clip) while
powering up the unit.
2.1.
Configuring the SS-100 for
Einstein Controllers
1.
Log into the Einstein and select
t o edit General Controller Information.
See Figure 2-3.
2.
Enable Full Options by selecting
Figure 2-3 - Alarm Annunciator Enable
3.
Scroll down to the Alarm Annunciator field
and type
a nd press
"
4.
Press
t hree times to reach the TCP/IP
screen. See Figure 2-4.
(
,
a nd
(
6
,
.
<
.