3.7 Bat Input

The maintenance bypass panel requires an input voltage of -48VDC protected with a 1 ⅓Amp
fuse from an external source.
Pin 1
GROUND
Pin 2
-BATTERY

3.8 Verify Installation Is Complete

utility position and verify that the commercial AC power takes over the loads. Move
the switch back to the
Page 16
© Copyright 2023 ABB. All rights reserved.
J7: -48VDC Battery Input
Compression Style Terminal
Block.
Figure 3-8: BAT Input Connections
3090125P-2
827E MBS_MAN
Compression
14 – 20 AWG
Rev. 2.4