- ページ 40
換気フード Miele DA 3496のPDF 操作およびインストール手順をオンラインで閲覧またはダウンロードできます。Miele DA 3496 48 ページ。
Miele DA 3496 にも: 操作およびインストール手順 (48 ページ), 操作およびインストール手順 (48 ページ), 操作およびインストール手順 (48 ページ)
Installation
If the exhaust air is to be ducted into
a flue, the ducting must be directed in
the flow direction of the flue.
Where ducting is horizontal, it must
be laid to slope away at at least 1 cm
per metre. This is to ensure that
condensate cannot drain back into
the cooker hood.
If the exhaust ducting is to run
through rooms, ceiling space etc.
there may be great variations in
temperature between the different
areas. The problem of condensation
will need to be addressed. The
exhaust ducting will need to be
suitably insulated.
Condensate trap
40
In addition to insulating the exhaust
ducting, we recommend that a suitable
condensate trap is also installed to
collect and evaporate any condensate
which may occur.
Condensate traps for 125 mm or
150 mm ducting are available as
optional accessories.
When installing a condensate trap,
ensure that it is positioned vertically
and as closely as possible above the
exhaust socket.
The arrow on the housing indicates
the direction of air-flow.
The condensate trap will be integrated
in cooker hoods which are designed to
be connected to an external motor
(EXT/EXTA models).
Silencer
To achieve even further reductions in
noise levels, a special silencer (optional
accessory) can be fitted in the ducting
system.