- ページ 39

冷蔵庫 Miele TX3587のPDF 操作およびインストール手順をオンラインで閲覧またはダウンロードできます。Miele TX3587 44 ページ。 Cooker hood
Miele TX3587 にも: 操作およびインストール手順 (48 ページ), 操作およびインストール手順 (48 ページ)

Miele TX3587 操作およびインストール手順
 When ducting is horizontal it must be
laid to slope away at at least 1 cm
per metre. This is to ensure that
condensate cannot drain back into
the rangehood.
 If the exhaust ducting is to run
through rooms, ceiling space etc.
where there may be great variations
in temperature between the different
areas, the problem of condensation
will need to be addressed. The
exhaust ducting will need to be
suitably insulated.

Condensate trap

In addition to insulating the exhaust
ducting, we recommend that a suitable
condensate trap is also installed to
collect and evaporate any condensate
which may occur.
Condensate traps are available for
125 mm or 150 mm ducting.
 When installing a condensate trap,
ensure that it is positioned vertically
and, if possible, directly above the
Connection for air extraction
exhaust socket.
The arrow on the housing indicates
the direction of airflow.
The condensate trap will be integrated
in rangehoods which are designed to
be connected to an external fan
(model......EXT).
39