2.6
Pin assignment
Details of the pin assignment can be found in the data
sheet for the corresponding valve.
3
ASSEMBLY
3.1
Safety instructions
WARNING!
Risk of injury from improper assembly.
▶ Assembly may only be carried out by authorized
technicians and with the appropriate tools.
Risk of injury from unintentional activation of the
system and uncontrolled restart.
▶ Secure system against unintentional activation.
▶ Following assembly, ensure a controlled restart.
3.2
Electrical connection
DANGER!
Risk of electric shock.
▶ Before reaching into the device, switch off the power
supply and secure to prevent reactivation.
▶ Observe applicable accident prevention and safety
regulations for electrical equipment.
7 mm max.
approx. 100 mm
Figure 1:
Remove cable insulation
Remove cable insulation to a length of approx. 100
mm (see „Figure 1").
Remove contact insert from housing (see „Figure 2").
Feed wire conductors under the strain relief through
the housing.
Remove the insulation from the wire conductors to a
max. length of 7 mm (1/4 ") (see „Figure 1").
Connect the cable plug in accordance with the pin
assignment of the valve. Tighten the screws on the
terminals to
max. 0.5 Nm (4.4 in-lb).
Re-fit the contact insert into the housing.
english
Lay the wire conductors beside one another under
the strain relief. Tighten the screws on the strain relief
to max. 0.5 Nm (4.4 in-lb).
Fit the cover and screw onto the housing.
Clamping piece
Cover
Screw
Figure 2:
Exploded view of cable plug Type 2509
3.3
Installing the cable plug
WARNING!
Risk of short circuit if the screw connection is not
sealed.
▶ Install in accordance with the National Electrical
Code (NEC) or Canadian Electrical Code (CEC), and
any applicable local codes, based on the installation
location.
▶ Ensure that the seal is fitted correctly.
▶ Carefully attach the cable plug.
The cable outlet can be rotated by 4 x 90°.
max. 6.75 Nm
Figure 3:
Installing the cable plug
Fit the conduit connection and tighten the screw con-
nection. Observe tightening torque of max. 6.75 Nm
(60 in-lb).
Use screw to attach the cable plug to the coil.
Observe tightening torque of max. 1.0 Nm (8.8 in-lb).
Seal
Contact insert
Housing
Strain relief
max. 1 Nm
Seal