General
The DTS-HAZ and DTS-HAZ-DC units are used for
temperature control and electrical termination of self-
regulating, constant wattage and mineral insulated (MI)
electric heating cables. Each kit contains the termina-
tions needed to make all electrical connections.

Explanation of Symbols Used:

Means WARNING.
Means Protective Earth (ground) terminal.
HAZARD OF ELECTRIC SHOCK. Disconnect all
power before starting. All installations must be
effectively grounded in accordance with the
National Electrical Code to eliminate shock
hazard.
Turn off power before removing junction box
cover at all times.
Users should install adequate controls and
safety devices with their electric heating
equipment. Where the consequences of failure
may be severe, back-up controls are essential.
Although the safety of the installation is re-
sponsibility of the user, Chromalox will be glad
to assist in making equipment rec ommenda-
tions.
The DTS-HAZ (or DTS-HAZ-DC) digital thermostat kit
is a microprocessor based temperature control and
power connection kit used for freeze protection or pro-
cess temperature maintenance of pipes or tanks pro-
tected by heat tracing products. This thermostat can
be used in ordinary areas as well as Class I, Div 2 or
IECEx/ATEX hazardous area locations.
Do not open when energized. Do not separate
when energized.
A disconnect device and circuit breaker should
be provided in the end installation. The instal-
lation and proximity for the disconnect device
must satisfy the electrical Authority having ju-
risdiction for the installation. Branch circuit
protection should be set for 40 amps or lower.
In all cases where the symbol is used on the
product, consult the documentation to find out
the nature of the potential hazard and any ac-
tions to be taken.