Warning
1
Warning
Danger: The top of the outdoor kit will
get very hot during operation. Keep
away from children. Install heater in a
location where the top of the kit cannot
be reached by small children.
Danger: Flue gas will be released
through the outdoor kit. Flue gas is very
hot and contains carbon monoxide. The
outdoor kit cannot be installed indoors.
To prevent risk of fire and carbon
monoxide
poisoning,
clearances
instructions.
Danger: Do not place or store any
combustible material within 5 feet of the
appliance. Maintain specified clearance
to combustibles on the wall where the
appliance is installed and any adjacent
walls
or
overhang.
clearances required in this manual.
Danger: Surface temperature of the kit
is less than 140°F, except highest top
surface which may reach 300°F.
Warning: Do not mount directly onto
vinyl siding, see Fig. 8.
This outdoor kit includes:
• Supports (2) with screws
• Sealing gasket
• Control panel shield
• Outdoor vent cap.
2
maintain
all
indicated
in
these
Observe
all
2

Selecting heater location

Before proceeding, read the water heater instructions
manual. If the information in that manual is not followed
exactly, a fire, explosion or poisoning by carbon
monoxide may result causing property damage,
personal injury or death.
B Choose an outside wall for the installation.
Installation on a wall protected by an overhang above
is recommended.
B Size the water and gas connections according to the
instructions in the water heater installation manual.
Use unions when connecting both water lines and
gas supply line to the heater.
Minimum clearances
If the appliance is installed under an overhang, there
must be a 36" clearance from the top of the appliance
and the mounting area must be open in front and on the
sides of the appliance.
Fig. 1
Ref.
Description
A
Directly below or adjacent to
an opening; operable
B
windows, doors and any fresh
air openings
C
D
From any adjacent wall
Below a gutter, sanitary
E
pipework, eaves or overhang
F
Above ground
From a gas meter or gas
G
regulator
Table 1 Clearances
Min.
distances
≥ 4 ft
≥ 4 ft
≥ 3 ft
≥ 1 ft
≥ 5 ft
6 720 608 835