FINAL INSPECTION & START UP
It is the responsibility of the installer to ensure that the tank will not float due to hydraulic conditions at the
site. Your local BIOBARRIER® Systems distributor may provide installation inspection services. If you have
questions, call Bio-Microbics at 1-800-753-3278 ((913)422-0707).
Persons coming in contact with wastewater, must immediately wash all exposed areas with disinfecting cleaner and
contact your personal physician. Failure to do so could result in severe sickness or death.
BEFORE THE UNIT IS BACKFILLED:
A. Open the vent/CIP ball valve from STEP 22 so that air can escape while filling the tank with water. This valve
MUST be closed prior to turning the system ON
B. Fill the tank to the normal operating level. AT LEAST 2 GALS OF ACTIVATED SLUDGE MUST BE PUT INTO
THE BIO BARRIER TANK.
C. Fill the tank to the normal operating level.
D. Check for leaks in all water-tight seals.
E. CLOSE THE VENT/CIP BALL VALVE.
F. Turn on power to the control panel. The green light will flash for ~5 seconds and then the blower will start.
Once the blower has started a robust boiling action should be present in the tank. The system is now in
automatic run mode.
G. Determine if excessive back pressure is present: Replace all access covers, place hand about 8 inches [20
cm] from BioBarrier
be upgraded.
H. Check for proper alarm function. Press the ENTER/MANUAL switch. The alarm should sound. Once this has
taken place press the ENTER/MANUAL switch again to return the system to automatic running mode. Use
the YELLOW FLOAT switch to activate the high water alarm of the system.
I.
Backfill the excavation.
J. Lastly, record the BioBarrier
NSF
CERTIFIED SYSTEMS SERVICE POLICY
All NSF (National Sanitation Foundation)/ANSI Standard 40 Class I / Standard 245 / Standard 350 Class R certified wastewater
treatment systems (BioBarrier
system's initial purchase price (two service calls per year). The NSF service calls ONLY cover NSF certified systems; other
components of the septic system are NOT covered.
If there are any deficiencies in the BioBarrier
writing and detail when these deficiencies can be fixed.
The company listed on the blower housing or control panel label performs this service. During an NSF service call, the service
company shall inspect the blower for proper operation, visually inspect the system's effluent for clarity, clean the blower air filter
and assure proper function of the control panel. If these service calls are not performed on your NSF certified system, or not
all of the items are checked, please call Bio-Microbics at:
For continual service of NSF certified systems beyond the first two years, an extended service agreement is available through
your local Distributor or current service provider. This policy should provide the same services and may include any additional
services that are required by local regulation.
vent, if air flow is felt then excessive back pressure exists and the system's vent must
®
unit's serial number in the Service Manual.
®
INTERNATIONAL
®
0.5, 0.5-N, 1.0, 1.0-N, 1.5, 1.5-N) have an initial two-year service agreement included with the
®
system's operation or components, the service person will notify the owner in
®
800-753-FAST(3278) or (913)422-0707