7b) Faults
Page 07.021.12
7. Functioning/Adjusting Instructions RZ-24-05 - cont.
Error
Detection loop cannot be
reset
Error LED lights up
permanently yellow
Key "Close door" does
not work
Key "RESET" does not
work
Electromagnets don't work Check the cable path from the terminal
Warning signal does not
work
© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • Germany
Tel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 20200513
Measure
Check whether the RZ-24-05 can be
reset with a 3.9 kΩ resistor on terminals
1 and 2. If not, check whether the
control module is correctly inserted in the
terminal board. If the problem persists,
replace the control module.
If resettable with a 3.9 kΩ resistor on
terminals 1 and 2, check the external
detection loop step by step. Is a 3.9 kΩ
resistor in the last detector? Is the manual
push button reset and is a correct contact
used?
Voltage from power supply too low?
Please measure.
External load too high?
Replace the power supply unit if
necessary.
Control module defective, replace it.
Replace the control module.
Replace the control module
board to the electromagnets.
Replace the terminal board.
Check the cable path from the terminal
board to the warning signal device.
Replace the terminal board.