- ページ 10
ドア開閉システム Dictator RZ-24-05 CentralのPDF テクニカル・マニュアルをオンラインで閲覧またはダウンロードできます。Dictator RZ-24-05 Central 13 ページ。
Dictator RZ-24-05 Central にも: テクニカル・マニュアル (12 ページ)
5.3 CONFIGURATION OF THE DIP SWITCHES
DIP switch 1
When DIP switch 1 is set to OFF (factory setting), a tripping is stored. This means that a manual
push button release is not automatically reset and the reset button must be operated manually.
DIP switch 1 in position ON realizes the automatic reset mode. This means that a tripping is
automatically reset after 3 s when the detection loop is ready.
DIP switch 2
The DIP switch 2 in position OFF (factory setting) realizes the central closing via the external
input. For this purpose, 24 V are briefly applied to the input. Central closing can be used to
close doors (only with electromagnets) without triggering the detection loop of the RZ-24-05.
This function is not a closing in case of fire, but only realizes the closing of the fire and smoke
protection closures, e.g. at the end of the working day. The electromagnet output is switched
off for approx. 3 s when the 24 V are applied to the external input.
The DIP switch 2 in position ON enables an external reset of the central via the external input
12 or 14.
10
DICTATOR Technik GmbH · +49 (0)821 246730 · [email protected] · en.dictator.de · 20.05.13
Technical manual: Central unit RZ-24-05
Control unit - back side
DIP switches for
operating modes
Ill. 3