- ページ 14

電源 Dictator RZ-24のPDF テクニカル・マニュアルをオンラインで閲覧またはダウンロードできます。Dictator RZ-24 19 ページ。 Central

Technical Manual
RZ-24 Central
Safe area
L1 N PE
14
Central
13
unit
12
RZ-24
-
11
10 +
9
8
7
-
+
6
5
-
4+
3
PE
2
N
1
L1
* Each ex-magnet has to be individually fused, with the fuse installed upstream of the magnet.
You can find more information in the manual of the magnets.
On site, the integration of a gas warning system must be checked by the ATEX representative
on the basis of explosion protection guidelines.
** Please refer to the Zener barrier manual for the detailed connection diagram.
5e) Cable Installation
Page 07.021.14
Electrical Connection and Installation of an Ex-
Proof Hold-Open System with RZ-24 - cont.
3
PE
2
N
1
L1
230 VAC
supply of the door
operator controller
AR* = cutoff relay for
If necessary,
door operator
2 ex-proof
CLOSE switches
Fuse*
5-
4-
7
8+
1+
Zener barrier
Z779**
Screening, optional
(operational earth)
The detection line and the tripping line are energized with low voltage.
Admissible laying systems are surface type with nail clamps, adhesive
clamps or spacing clamps, in open or closed tubes, cable ducts and
profile rails and flush type in slots or tubes.
For cabling you need:
a. Fire detection line: e.g. Ölflex EB 2x0.75 mm
Mark intrinsically safe current circuits light blue and lay them sepa-
rately (see DIN EN 60079-14).
b. Hold-open system: see description of the ex-proof electromagnets
c.
Power line:
© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • Germany
Tel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 20220325
Hazardous area zones 1 - 2
Up to 12 electromagnets
EM GD 50 EX or EM GD
70 EX
Max. 20 intrinsically safe
RM 3000IS EX smoke detectors or
WM 3000IS EX heat detectors
NYM-J 3x1.5 mm
2
Ex-proof hand
release switch
with
700232
resistor
3,9 kΩ
Ill. 6b
2