- ページ 13
電源 Dictator RZ-24-05 CentralのPDF テクニカル・マニュアルをオンラインで閲覧またはダウンロードできます。Dictator RZ-24-05 Central 13 ページ。
Dictator RZ-24-05 Central にも: テクニカル・マニュアル (12 ページ)
Technical manual: Central unit RZ-24-05
7.2 TROUBLESHOOTING
Error
Detection loop cannot
be reset
Error LED lights up per-
manently yellow
Key "Close door" does
not work
Key "RESET" does not
work
Electromagnets don't
work
Warning signal does not
work
DICTATOR Technik GmbH · +49 (0)821 246730 · [email protected] · en.dictator.de · 20.05.13
Measure
Check whether the RZ-24-05 can be reset with a 3.9 kΩ resistor
on terminals and 2. If not, check whether the control module is
correctly inserted in the terminal board. If the problem persists,
replace the control module. If resettable with a 3.9 kΩ resistor on
terminals 1 and 2, check the external detection loop step by step.
Is a 3.9 kΩ resistor in the last detector? Is the manual push button
reset and is a correct contact used?
Voltage from power supply too low? Please measure.
External load too high? Replace the power supply unit if neces-
sary.
Control module defective, replace it.
Replace the control module.
Replace the control module.
Check the cable path from the terminal board to the electromag-
nets.
Replace the terminal board.
Check the cable path from the terminal board to the warning
signal device.
Replace the terminal board.
Protronic
Z-6.510-2435
VDS
13