- ページ 11

コントローラー ABB COM610のPDF 製品マニュアルをオンラインで閲覧またはダウンロードできます。ABB COM610 12 ページ。 Communication gateway

ABB COM610 製品マニュアル
Communication Gateway
Table 4: Electromagnetic compatibility tests
Test
Power frequency (50 Hz) magnetic
field
Voltage dips and short interruptions
Emission test
Table 5: Climatic environmental tests
Test
Dry heat test
Cold test
Damp heat, cyclic
Storage
Table 6: Mechanical tests
Test
Vibration tests
Shock and bump tests
Seismic test
Reference
IEC 61000-4-8
IEC 61000-4-11
EN 55011
IEC 60255-25
Reference
IEC 60068-2-2
IEC 60068-2-1
IEC 60068-2-30
IEC 60068-2-48
Reference
IEC 60068-2-6
IEC 60255-21-1
IEC 60068-2-27
IEC 60068-2-29
IEC 60255-21-2
IEC 60255-21-3
COM610
1MRS755425
Requirement
300 A/m, continuous
30% reduction for 10 ms
60% reduction for 100 ms
60% reduction for 1000 ms
>95% reduction for 5000 ms
class A
Requirement
+55°C, 96 hours
+70°C, 4 hours
-10°C, 96 hours
-25°C, 4 hours
+25°...55°C, Rh > 93%
6 cycles (12h+12h)
+70°C, 72 hours
-40°C, 72 hours
Requirement
Vibration response test:
- f = 10...150 Hz
- ± 0.035 mm, 10...58 Hz
2
- 5 m/s
, 58...150 Hz
Vibration endurance test:
- f = 10...150 Hz
- ± 0.075 mm, 10...58 Hz
2
- 10 m/s
, 58...150 Hz
Shock response test:
- peak acceleration: 5 x g
n
- pulse duration: 11 ms
- numbers of pulses in each dire-
tion: 3
Shock withstand test:
- peak acceleration: 15 x g
n
- duration of the pulse: 11 ms
- number of pulses in each direc-
tion: 3
Bump test:
- peak acceleration: 10 x g
n
- pulse duration: 16 ms
- number of pulses in each direc-
tion: 1000
Test method B:
biaxial multi-frequency random
seismic test
- 2 x g
in horizontal direction
n
- 1 x g
in vertical direction
n
11