- ページ 3

ランタン CREE LIGHTING KBLのPDF 取付説明書をオンラインで閲覧またはダウンロードできます。CREE LIGHTING KBL 6 ページ。 Led, universal hook and cord or pendant mount

6
Reflector
7
Screw
8
Heatsink

ELECTRICAL CONNECTIONS

STEP 1:
Make the following Electrical Connections:
a. For 120/277/347V connect the black fixture lead to the
voltage supply or Hot 1 (for 208/240/480V wiring).
b. For 120/277/347V connect the white fixture lead to the
neutral supply or Hot 2 (for 208/240/480V wiring).
c. Connect the green or green/yellow ground lead to the green
wire position of the terminal block.
STEP 2:
For Dimming make the following Electrical Connections:
NOTE: The incoming signal cable needs to pass through the 1/2"
knockout shown in Figure 3 on page 2.
d. If 0/1-10V Dimming is used, connect the violet lead to the
supply positive dimming lead. If dimming is not being used
ensure to cap off the violet lead.
e. If 0/1-10V Dimming is used, connect the gray lead to the
supply negative dimming lead. If dimming is not being used
ensure to cap off the gray lead.
3 of 6
Hinge Retainer
Frame Hinge
Mounting Ring
Reflector
Lens with V-band
Safety Cable

STANDARD REFLECTOR:

STEP 1:
Loosen the (4) screws, shown in Figure 5, at least 0.1 inch from the
heatsink.
NOTE: The view in Figure 5 is of the underside of the luminaire.
STEP 2:
Bring trim into housing and line up the (4) screws from Step 1, with the
keyhole slots on the reflector.
STEP 3:
Rotate trim, turn clockwise and tighten the (4) screws from Step 1.
Mounting Lens or Wire Guard To Aluminum Reflector
STEP 1:
Secure the hinge retainer and frame hinge to the reflector using
supplied screw and lock nut. See Figure 6.
NOTE: Reflector is pre-punched at position of this installation.
STEP 2:
Swing the wire guard into place and secure to the reflector with the
attached spring latch. See Figure 6.
Mounting Lens or Wire Guard To Prismatic/ Polycarbonate
Reflector
STEP 1:
Place lens or wire guard onto the bottom of reflector, and place V-band
around lens and reflector. See Figure 7.
STEP 2:
Secure lens or wire guard to reflector by tightening screw on V-band.
See Figure 7.
INSTALLING SAFETY CABLE
NOTE: Safety Cable is sold separately as an accessory, please refer
to installation sheet in safety cable packaging for complete installing
instructions.
STEP 1:
Attach one end of the safety cable through the fin of the heatsink. See
Figure 8.
STEP 2:
Attach other end of the safety cable to mounting surfaces using
customer supplied hardware.
LINE
OR HOT 1
GREEN
GROUND-GREEN
NEUTRAL
NEUTRAL-WHITE
OR HOT 2
VIOLET
GREY
LUMINAIRE
LINE-BLACK
DIM (+) VIOLET
DIM (-) GREY
LPN00513X0001A4_D