8. Remove the red cap from the gray cable that was left coiled inside the receptacle box (in step 4).
Connect the gray cable to the cable port on the back of the receptacle box faceplate. Push the cable
connector into the port until there is a click and the cable connector cannot be pulled out of the port.
9. Attach the faceplate to the receptacle box with the 2 white screws.
10. Position the desk mount alarm unit in the desired location (within 12 feet of the receptacle outlet)
and connect the cable to the receptacle outlet by pushing the cable connector into the port until
there is a click and the cable connector cannot be pulled out of the port.
VI. WALL MOUNT ALARM
Wall Mount Alarm Installation - Models #38002, #38004 and #34064
1. Select an appropriate location for the wall alarm unit to be installed. The wall alarm should be
installed at a convenient height for viewing and operating (approximately 5 feet from the floor).
2. Attach the wall alarm's receptacle box to wall studs at desired height from the floor.
3. Thread the gray cable through one of the knockout holes in the receptacle box. Keep 6 to 8 inches
of the end of the cable coiled inside the box.
4. To prevent joint compound and other debris from getting into the alarm's receptacle box during
building construction, cover the receptacle box opening with masking or duct tape (seal tape at
receptacle box mud ring).
5. Run the length of the gray cable to the tank room. Coil the end of the hose a minimum of 6 to 8
inches at the end of the oxygen gas line in the tank room.
6. Anchor the running gray cable to the studs and to the frame of the building.
CAUTION: DO NOT NAIL OR STAPLE THROUGH THE CABLE. ANY BREAK IN THE CABLE
INSULATION MIGHT COMPROMISE THE SYSTEM'S INTEGRITY AND CAUSE THE ALARM
TO NOT OPERATE PROPERLY.
Note: The gray cable is 100 ft long. Contact Accutron, Inc., at 800-531-2221 if additional
cable is required.
7. Take the wall alarm unit from the shipping carton and remove the plastic wrap. Separate the face-
plate from the alarm unit by pushing the center pin of the two-part white snap rivet out from the
backside of the faceplate's aluminum sub plate. The aluminum sub plate remains attached to the
alarm unit.
Note: Pushing the center pin of the rivet from the front of the faceplate could scratch
the faceplate.
8. Remove the red cap from the gray cable that was left coiled inside the receptacle box (in step 3).
Connect the gray cable to the cable port on the back of the alarm unit's sub plate. Push the cable
connector into the port until there is a click and the cable connector cannot be pulled out of the port.
7