Installation
2.2 Mounting and attaching the bus cable(s)
3. Shorten the braided shield and foil shield to a length of approximately 12 mm (the foil shield
can be left somewhat longer) and shorten the two fillers to a length of approximately 12 mm.
4. Fold back the braid shield over the cable jacket.
5. Strip approximately 10 mm from the end of the wires.
6. Fit the bus cable to the terminal so that the braided shield is lying directly under the cable
clamp.
7. Screw the ends of the wires to the appropriate terminals (if the cores are stranded, for
example, the trailing cable, 0.25 mm
used).
8. If the bus terminal is at the start or end of a segment, the integrated terminator must be
activated (switch set to Termination on).
Note
The shield clamps are used solely to contact the shields and are not suitable as strainrelief
clamps. This means that the bus cables must be secured as close as possible to the 12M bus
terminals to provide mechanical strain relief.
Note
If the terminating resistor is activated (permitted only at the segment ends), the terminal pair
A1, B1 must be used (A2, B2 are disconnected from the segment).
During operation of the bus terminal in the segment, it requires 5 V to be supplied by the DTE.
The DTE must therefore be turned on and the D-sub male connector inserted and secured by
screws! Due to the necessary termination at the start and end of the segment, the DTE
connected there must not be turned off.
Note
The same wires (green or red) must always be connected to the same terminal A or B in all bus
terminals (and with all bus connectors) and be uniform throughout the segment.
16
Filler
Foil shield
Fold back braided shield over the cable jacket
2
wireend ferrules complying with DIN 46228 must be
Operating Instructions, 06/2022, C79000-G8976-C333-02
12M bus terminal