- ページ 17

産業機器 Siemens SIMATIC RTLS4030GのPDF 取扱説明書をオンラインで閲覧またはダウンロードできます。Siemens SIMATIC RTLS4030G 34 ページ。 Localization systems
Siemens SIMATIC RTLS4030G にも: 機器マニュアル (19 ページ), 取扱説明書 (26 ページ)

Siemens SIMATIC RTLS4030G 取扱説明書
Installation & Operation
3.1

Notes on installation

Power supply
The gateway is designed for operation with a directly connectable safety extra-low voltage
(SELV) from a limited power source (LPS). The power supply therefore needs to meet at
least one of the following conditions:
• Only safety extra low voltage (SELV) with limited power source (LPS) complying with IEC
• The power supply unit for the gateway must meet NEC Class 2 according to the National
Note
Before you install the gateways, read this section carefully to ensure problem-free installation
and commissioning.
The gateways can only be used in conjunction with the RTLS localization system.
The gateway is intended for fixed installation on walls or ceilings. Installation is to be
performed by qualified and trained users according to the operating instructions. In addition,
installation must take place in accordance with the respective instructions for the installation
of electrical systems and utilities. The gateways must be installed so that they are accessible
for future maintenance, e.g., for opening the enclosure cover.
Note the specifications in the section "Technical specifications (Page 25)" during installation
and operation. Ensure that all screws are securely and firmly screwed into the wall/ceiling and
can support the weight of the gateway and its wiring.
Make sure that the ambient temperature does not exceed 50 °C and that the gateway is not
installed in a location where it is exposed to direct sunlight.
SIMATIC RTLS4030G
Operating Instructions, 05/2023, C79000-G8976-C515-10
WARNING
61140 / EN 62368-1 can be connected to the power supply terminals.
Electrical Code (r) (ANSI / NFPA 70).
3
17