Micro Automation Set 14
3.
Remove the write protection of the
MicroBox PC 420.
Open the MS DOS prompt and enter the
following command to
deactivate:
ewfmgr c: -commitanddisable
activate:
ewfmgr c: -enable
the write mode.
4.
The following network settings have to be
applied on the used network card of the
MicroBox PC 420:
IP address:
Subnet mask: 255.255.255.0
5.
Install SIMATIC NET Edition 2005.
6.
Install WinAC 2005 RTX.
7.
Open the Station Configuration Editor
(
) in the task bar
Change the station name to
"WinAC_Station"
Assign slot 2 to WinLC RTX
Add the "IE-General" module on slot
3
8.
Open the included WinAC project
"Set14_WinAC_V2-0.zip" on your
configuration PC using STEP 7 and make
the following settings in STEP 7:
Set the access point in "Set PG/PC
Interface" to "S7ONLINE
TCP/IP(Auto) network controller"
V2.0
Entry ID 21062588
192.168.2.140
05/18/05